SiriuxUser - Table of Contents

Section CANopen

Unit Type Memory PDO CAN

1000h - Device Type

  UNSIGNED32 ROM no ro

1001h - Error Register

  UNSIGNED8 RAM yes ro

1003h - Pre-defined Error Field

  UNSIGNED32

Subindex 0 - Number of Errors

  UNSIGNED8 RAM no rw

Subindex 1 - Standard Error Field

  UNSIGNED32 RAM no ro

Subindex 8 - Standard Error Field

  UNSIGNED32 RAM no ro

1005h - COB-ID SYNC

  UNSIGNED32 EEPROM no rw

1008h - Manufacturer Device Name

  VISIBLE_STRING ROM no ro

100Ah - Manufacturer Software Version

  VISIBLE_STRING ROM no ro

1010h - Store Parameter Field

  STORAGE

Subindex 0 - Number of Entries

  UNSIGNED8 RAM no ro

Subindex 1 - All Parameters

  UNSIGNED32 RAM no rw

Subindex 2 - Communication Parameters (1000h-1FFFh)

  UNSIGNED32 RAM no rw

Subindex 3 - application parameters (2000h-2700h)

  UNSIGNED32 RAM no rw

1011h - Restore Default Parameters

  STORAGE

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - All Parameters

  UNSIGNED32 RAM no rw

Subindex 2 - Communication Parameters (1000h-1FFFh)

  UNSIGNED32 RAM no rw

Subindex 3 - Application Parameters (2000h-27FFh)

  UNSIGNED32 RAM no rw

1012h - COB-ID Time Stamp

  UNSIGNED32 EEPROM no rw

1014h - COB-ID EMCY

  UNSIGNED32 EEPROM no rw

1016h - Consumer Heartbeat Time

  UNSIGNED32

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - Consumer Heartbeat Time (I/O Module)

  UNSIGNED32 EEPROM no rw

1017h - Producer Heartbeat Time

  UNSIGNED16 EEPROM no rw

1018h - Identity Object

  IDENTITY

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - Vendor Id

  UNSIGNED32 ROM no ro

Subindex 2 - Product Code

  UNSIGNED32 EEPROM no ro

Subindex 3 - Revision number

  UNSIGNED32 ROM no ro

Subindex 4 - Serial number

Number UNSIGNED32 EEPROM no ro

1200h - Server SDO Parameter 1

  SDO_COMM_PAR

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - COB-ID Client -> Server

  UNSIGNED32 ROM no ro

Subindex 2 - COB-ID Server -> Client

  UNSIGNED32 ROM no ro

1400h - Receive PDO Communication Parameter 1

  PDO_COMM_PAR

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - COB-ID

  UNSIGNED32 EEPROM no rw

Subindex 2 - Transmission Type

  UNSIGNED8 EEPROM no rw

1600h - Receive PDO Mapping Parameter 1

  PDO_MAPPING

Subindex 0 - Number of Entries

  UNSIGNED8 EEPROM no rw

Subindex 1 - Mapping Entry 1

  UNSIGNED32 EEPROM no rw

Subindex 8 - Mapping Entry 8

  UNSIGNED32 EEPROM no rw

1800h - Transmit PDO Communication Parameter 1

  PDO_COMM_PAR

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - COB-ID

  UNSIGNED32 EEPROM no rw

Subindex 2 - Transmission Type

  UNSIGNED8 EEPROM no rw

Subindex 3 - Inhibit Time

  UNSIGNED16 EEPROM no rw

Subindex 4 - Compatibility Entry

  UNSIGNED8 EEPROM no rw

Subindex 5 - Event Timer

  UNSIGNED16 EEPROM no rw

1801h - Transmit PDO Communication Parameter 2

  PDO_COMM_PAR

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - COB-ID

  UNSIGNED32 EEPROM no rw

Subindex 2 - Transmission Type

  UNSIGNED8 EEPROM no rw

Subindex 3 - Inhibit Time

  UNSIGNED16 EEPROM no rw

Subindex 4 - Compatibility Entry

  UNSIGNED8 EEPROM no rw

Subindex 5 - Event Timer

  UNSIGNED16 EEPROM no rw

1802h - Transmit MPDO Communication Parameter 3

  PDO_COMM_PAR

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - COB-ID

  UNSIGNED32 EEPROM no rw

Subindex 2 - Transmission Type

  UNSIGNED8 ROM no ro

Subindex 3 - Inhibit Time

  UNSIGNED16 EEPROM no rw

Subindex 4 - Compatibility Entry

  UNSIGNED8 EEPROM no rw

Subindex 5 - Event Timer

  UNSIGNED16 EEPROM no rw

1A00h - Transmit PDO Mapping Parameter 1

  PDO_MAPPING

Subindex 0 - Number of Entries

  UNSIGNED8 EEPROM no rw

Subindex 1 - Mapping Entry 1

  UNSIGNED32 EEPROM no rw

Subindex 8 - Mapping Entry 8

  UNSIGNED32 EEPROM no rw

1A01h - Transmit PDO Mapping Parameter 2

  PDO_MAPPING

Subindex 0 - Number of Entries

  UNSIGNED8 EEPROM no rw

Subindex 1 - Mapping Entry 1

  UNSIGNED32 EEPROM no rw

Subindex 8 - Mapping Entry 8

  UNSIGNED32 EEPROM no rw

1A02h - Transmit MPDO Mapping Parameter 3

  PDO_MAPPING

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

1FA0h - Object Scanner List

  UNSIGNED32

Subindex 0 - Number of Entries

  UNSIGNED8 ROM no ro

Subindex 1 - Scanner Entry 1

  UNSIGNED32 EEPROM no rw

Section Control

Unit Type Memory PDO CAN

2000h - Pump Setpoint

0.01 Percent SIGNED16 EEPROM no wo

2001h - Pump Control Mode

Select UNSIGNED8 EEPROM no wo

2002h - Pump Command

Bitset UNSIGNED8 EEPROM no wo

2008h - Bus Setpoint

0.01 Percent SIGNED16 EEPROM yes wo

2009h - Bus Control Mode

Select UNSIGNED8 EEPROM yes wo

200Ah - Bus Command

Bitset UNSIGNED8 EEPROM yes wo

Section Status

Unit Type Memory PDO CAN

2040h - System Actual Capacity

0.01 Percent SIGNED16 RAM yes ro

2041h - System Control Mode

Select UNSIGNED8 RAM yes ro

2042h - System Command

Bitset UNSIGNED8 RAM yes ro

2048h - Wanted Setpoint

0.01 Percent SIGNED16 RAM yes ro

2049h - Wanted Control Mode

Select UNSIGNED8 RAM yes ro

204Ah - Wanted Command

Bitset UNSIGNED8 RAM yes ro

2050h - Controller Status (System)

Bitset UNSIGNED8 RAM yes ro

2052h - Operation Status (System)

Bitset UNSIGNED8 RAM yes ro

2054h - Bus Status

Bitset UNSIGNED8 RAM yes ro

2056h - Control Status

Bitset UNSIGNED8 RAM yes ro

2058h - Ready for Operation (DP/MP)

Bitset UNSIGNED8 RAM yes ro

205Ah - Pump is Operating (DP/MP)

Bitset UNSIGNED8 RAM yes ro

205Ch - Service Required (DP/MP)

Bitset UNSIGNED8 RAM yes ro

205Eh - Warning Present (DP/MP)

Bitset UNSIGNED8 RAM yes ro

2060h - Error Present (DP/MP)

Bitset UNSIGNED8 RAM yes ro

2062h - Final Error Present (DP/MP)

Bitset UNSIGNED8 RAM yes ro

2064h - Rotating Direction (DP/MP)

Bit UNSIGNED8 RAM yes ro

206Eh - Number of DP/MP Pumps

Number UNSIGNED8 RAM yes rwr

2070h - Pump Digital Outputs

Bitset UNSIGNED8 RAM yes ro

2072h - Pump Digital Inputs

Bitset UNSIGNED8 RAM yes ro

2076h - IF-Module

Select UNSIGNED8 RAM no ro

Section Measurement

Unit Type Memory PDO CAN

2083h - Speed (DP/MP)

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Master Speed

1 rpm UNSIGNED16 RAM yes ro

Subindex 2 - Slave 1 or DP Slave Speed

1 rpm UNSIGNED16 RAM yes ro

2087h - Estimated Flow (System)

0.1 m3/h UNSIGNED16 RAM yes ro

2088h - Estimated Flow Range Min (System)

0.1 m3/h UNSIGNED16 RAM yes ro

2089h - Estimated Flow Range Max (System)

0.1 m3/h UNSIGNED16 RAM yes ro

208Bh - Estimated Pressure (System)

0.1 kPa UNSIGNED16 RAM yes ro

208Ch - Estimated Pressure Range Min (System)

0.1 kPa UNSIGNED16 RAM yes ro

208Dh - Estimated Pressure Range Max (System)

0.1 kPa UNSIGNED16 RAM yes ro

2090h - Power Rating (System)

0.001 W UNSIGNED32 RAM yes ro

2091h - Current (System)

0.001 A UNSIGNED32 RAM yes ro

2092h - Voltage Level (DP/MP)

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Voltage Level (Master)

1 V UNSIGNED16 RAM yes ro

Subindex 2 - Voltage Level (Slave 1)

1 V UNSIGNED16 RAM yes ro

2093h - Power Rating (DP/MP)

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Power Rating (Master)

0.001 W UNSIGNED32 RAM yes ro

Subindex 2 - Power Rating (Slave 1)

0.001 W UNSIGNED32 RAM yes ro

2094h - Current (DP/MP)

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Current (Master)

0.001 A UNSIGNED32 RAM yes ro

Subindex 2 - Current (Slave 1)

0.001 A UNSIGNED32 RAM yes ro

20A0h - Medium Temperature (System)

0.1 K UNSIGNED16 RAM yes ro

Section Messaging (Service and Errors)

Unit Type Memory PDO CAN

20C1h - Current Warning/Error

Error Code UNSIGNED8 RAM yes ro

20C2h - Current Warning/Error (DP/MP)

  UNSIGNED8

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Current Warning/Error (Master)

Error Code UNSIGNED8 RAM yes ro

Subindex 2 - Current Warning/Error (Slave 1)

Error Code UNSIGNED8 RAM yes ro

20E0h - Error History Code (Master)

  UNSIGNED8

Subindex 0 - Number of Entries

Number UNSIGNED8 EEPROM no ro

Subindex 1 - Error_t

Error Code UNSIGNED8 EEPROM no ro

Subindex 16 - Error_t-15

Error Code UNSIGNED8 EEPROM no ro

20E1h - Error History Code (Slave 1)

  UNSIGNED8

Subindex 0 - Number of Entries

Number UNSIGNED8 EEPROM no ro

Subindex 1 - Error_t

Error Code UNSIGNED8 EEPROM no ro

Subindex 16 - Error_t-15

Error Code UNSIGNED8 EEPROM no ro

Section Statistic

Unit Type Memory PDO CAN

2101h - Operation Time Resettable (System)

1 Minutes UNSIGNED32 EEPROM no rw

2103h - Operation Time Resettable

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Operation Time Resettable (Master)

1 Minutes UNSIGNED32 EEPROM no rw

Subindex 2 - Operation Time Resettable (Slave 1)

1 Minutes UNSIGNED32 EEPROM no rw

2104h - Operation Peak Load Time Resettable

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - One pump running

1 Minutes UNSIGNED32 EEPROM no ro

Subindex 2 - Two pumps running

1 Minutes UNSIGNED32 EEPROM no ro

2108h - Power On Time

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Power On Time (Master)

1 Minutes UNSIGNED32 EEPROM no ro

Subindex 2 - Power On Time (Slave 1)

1 Minutes UNSIGNED32 EEPROM no ro

2109h - Uptime

1 Minutes UNSIGNED32 RAM no ro

2110h - Power On Counter

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Power On Counter (Master)

Number UNSIGNED16 EEPROM no ro

Subindex 2 - Power On Counter (Slave 1)

Number UNSIGNED16 EEPROM no ro

2111h - Pump Kick Counter

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Pump Kick Counter (Master)

Number UNSIGNED16 EEPROM no ro

Subindex 2 - Pump Kick Counter (Slave 1)

Number UNSIGNED16 EEPROM no ro

2112h - Auto Night Mode Counter

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Auto Night Mode Counter (Master)

Number UNSIGNED16 EEPROM no ro

Subindex 2 - Auto Night Mode Counter (Slave 1)

Number UNSIGNED16 EEPROM no ro

2113h - Consumption (System)

0,1 kWh UNSIGNED32 EEPROM no ro

2114h - Consumption

  UNSIGNED32

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Consumption (Master)

0,1 kWh UNSIGNED32 EEPROM no ro

Subindex 2 - Consumption (Slave 1)

0,1 kWh UNSIGNED32 EEPROM no ro

212Fh - Q-Histogramm

  UNSIGNED16

Subindex 0 - Number of Entries (n)

Number UNSIGNED8 EEPROM no ro

Subindex 1 - Histogram 0% - 20%

0.01 Percent UNSIGNED16 EEPROM no ro

Subindex 2 - Histogram 20% - 40%

0.01 Percent UNSIGNED16 EEPROM no ro

Subindex 3 - Histogram 40% - 60%

0.01 Percent UNSIGNED16 EEPROM no ro

Subindex 4 - Histogram 60% - 80%

0.01 Percent UNSIGNED16 EEPROM no ro

Subindex 5 - Histogram 80% - 100%

0.01 Percent UNSIGNED16 EEPROM no ro

Section Constants

Unit Type Memory PDO CAN

2182h - Pump Type

  UNSIGNED16

Subindex 0 - Number of Entries

Number UNSIGNED8 RAM no ro

Subindex 1 - Pump Type (Master)

Select UNSIGNED16 EEPROM no ro

Subindex 2 - Pump Type (Slave 1)

Select UNSIGNED16 RAM no ro

218Bh - Pump Type Name

Version UNICODE_STRING ROM no ro

218Ch - This Pump Function

Text UNICODE_STRING EEPROM no rw

218Dh - This Pump Location/Name

Text UNICODE_STRING EEPROM no rw

21A0h - Min Speed (System, CONST_SPEED)

1 rpm UNSIGNED16 ROM no ro

21A1h - Max Speed (CONST_SPEED)

1 rpm UNSIGNED16 ROM no ro

21A4h - Min Pressure dp-v (VAR_DIFFPRESS)

0.1 kPa UNSIGNED16 ROM no ro

21A5h - Max Pressure dp-v (VAR_DIFFPRESS)

0.1 kPa UNSIGNED16 ROM no ro

21A7h - Max Flow

0.1 m3/h UNSIGNED16 ROM no ro

21A8h - Min Medium Temperature

0.1 K UNSIGNED16 ROM no ro

21A9h - Max Medium Temperature

0.1 K UNSIGNED16 ROM no ro

21ABh - Max Power Rating

0.001 W UNSIGNED32 ROM no ro

21ACh - Min Pressure dp-c (CONST_DIFFPRESS)

0.1 kPa UNSIGNED16 ROM no ro

21ADh - Max Pressure dp-c (CONST_DIFFPRESS)

0.1 kPa UNSIGNED16 ROM no ro

Section Configuration

Unit Type Memory PDO CAN

2201h - dp-c = f(T) Regulation Tmin

0.1 K UNSIGNED16 EEPROM no rw

2202h - dp-c = f(T) Regulation Tmax

0.1 K UNSIGNED16 EEPROM no rw

2203h - dp-c = f(T) Regulation Pmin

0.1 kPa UNSIGNED16 EEPROM no rw

2204h - dp-c = f(T) Regulation Pmax

0.1 kPa UNSIGNED16 EEPROM no rw

2207h - HV/AC System Error Detection

Select UNSIGNED8 EEPROM no rw

2208h - Error Auto Reset Time

1 s UNSIGNED16 EEPROM no rw

2229h - Automatic Night Mode

Select UNSIGNED8 EEPROM no rw

2232h - SBM Relay Mode

Select UNSIGNED8 EEPROM no rw

2233h - SSM Relay Mode

Select UNSIGNED8 EEPROM no rw

2234h - 0-10V Setpoint Mode

Select UNSIGNED8 EEPROM no rw

2235h - 0-10V Activate

Bit UNSIGNED8 EEPROM no rw

2250h - Pump Kick Event

Event UNSIGNED8 RAM no rw

2251h - Pump Kick Time

Hour SIGNED8 EEPROM no rw

225Bh - Menu lock

Bit UNSIGNED8 EEPROM no ro

225Dh - Display Orientation

Select UNSIGNED8 EEPROM no rw

225Eh - Display Unit

Select UNSIGNED8 EEPROM no rw

Section Double/Multi Pump

Unit Type Memory PDO CAN

2315h - DP-Modus

Select UNSIGNED8 EEPROM no rw

2320h - Pump Swap Event

Event UNSIGNED8 RAM no rw

2322h - Pump Swap Time (DP/MP)

1 Hour SIGNED8 EEPROM no rw

2323h - Member Pump Enable

Bitset UNSIGNED8 EEPROM yes rww

Section CAN Configuration

Unit Type Memory PDO CAN

2400h - CANopen Address

CANAddress UNSIGNED8 EEPROM no rw

2403h - Auto Operational Mode

1 s UNSIGNED8 EEPROM no rw

SiriuxUser - Parameter Documentation


Section CANopen

1000h - Device Type

Contains information about the device type. The lower 16 bit contain the Device Profile Number and the upper 16 bit contain the Additional Information. The Wilo CAN bus contains the value 0000 0000h (deviceprofile 0000h and no additional information).

Note: For more information see CiA Draft Standard 301, Version 4.02, page 86

Variable Type: UNSIGNED32, ROM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1001h - Error Register

The error register is a field of 8 bits, each for a certain error type. If an error occurs the bit has to be set. Wilo Pumps only support Generic Error and Manufacturer Error.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 87

Bit Bit equals Zero Bit equals One
0 generic error
1 current
2 voltage
3 temperature
4 communication error (overrun, error state)
5 device profile specific
6 reserved
7 manufacturer error
Variable Type: UNSIGNED8, RAM Formatting:  
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

1003h - Pre-defined Error Field

This object holds errors that have occurred on the device and have been signalled via Emergency Object. It is an error history. Writing to sub index 0 deletes the entire error history. The values in this parameter are not stored in EEPROM, for a more detailed error history list see Par 20E0h - Error History Code (Master), Par 20E6h - Error History Date (Master) and Par 20ECh - Error History Operation Hours (Master).

Note: For more information see CiA Draft Standard 301, Version 4.02, page 88

SubIndex Name Variable Type Default Value
1003h Subindex 0 Number of Errors UNSIGNED8 0
1003h Subindex 1 Standard Error Field UNSIGNED32 0
1003h Subindex 2 Standard Error Field UNSIGNED32 0
1003h Subindex 3 Standard Error Field UNSIGNED32 0
1003h Subindex 4 Standard Error Field UNSIGNED32 0
1003h Subindex 5 Standard Error Field UNSIGNED32 0
1003h Subindex 6 Standard Error Field UNSIGNED32 0
1003h Subindex 7 Standard Error Field UNSIGNED32 0
1003h Subindex 8 Standard Error Field UNSIGNED32 0
1003h Subindex 0 - Number of Errors

This Subindex contains the number of following subindexes.

Note: This Subindex is writeable, but only the value 0 is accepted, any other value generates an abort message (error code: 0609 0030h).

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, RAM Formatting:  
Value: 0 to 0xFE Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

1003h Subindex 1 - Standard Error Field

This Subindex contains a record of the last signalled error.

Variable Type: UNSIGNED32, RAM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

1003h Subindex 8 - Standard Error Field

This Subindex contains a record of the 8th last signalled error.

Variable Type: UNSIGNED32, RAM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

1005h - COB-ID SYNC

COB-ID of the Synchronization object. The device listens to the SYNC COB-ID written in this message.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 89.

Note: The bits 29 and 30 are not supported and must be 0.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: 0x80, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1008h - Manufacturer Device Name

Contains the device name (Example: 'Stratos 30/1-12').

Note: For more information see CiA Draft Standard 301, Version 4.02, page 91

Variable Type: VISIBLE_STRING, ROM Formatting:  
Value: 0 to 32 Default, Error: "Siriux", n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

100Ah - Manufacturer Software Version

Pump software number (Example: '5.02').

Note: For more information see CiA Draft Standard 301, Version 4.02, page 91

Variable Type: VISIBLE_STRING, ROM Formatting:  
Value: 0 to 6 Default, Error: "", n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1010h - Store Parameter Field

This entry supports saving of parameters in non volatile memory. With a read access the device provides information about its saving capabilities. Several parameter groups are distinguished. To save, the signature 'save' (0x65766173) must be written to the wanted Subindex.

Wilo devices support only save on demand for the communication parameters (0x1000 to 0x1FFF), the application parameters (0x2000 to 0x27FF) are saved directly when they are changed.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 92.

SubIndex Name Variable Type Default Value
1010h Subindex 0 Number of Entries UNSIGNED8 calc
1010h Subindex 1 All Parameters UNSIGNED32 0
1010h Subindex 2 Communication Parameters (1000h-1FFFh) UNSIGNED32 1
1010h Subindex 3 application parameters (2000h-2700h) UNSIGNED32 2
1010h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, RAM Formatting:  
Value: 0 to 0x7F Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1010h Subindex 1 - All Parameters

This Subindex is not supported.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1010h Subindex 2 - Communication Parameters (1000h-1FFFh)

When this subindex is written, the current Communication Parameters (0x1000-0x1FFF) are stored in EEPROM.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1010h Subindex 3 - application parameters (2000h-2700h)

This Subindex is not supported.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 2, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1011h - Restore Default Parameters

Several parameter groups are distinguished. To restore from EEPROM, the signature 'load' (0x64616f6c) must be written to the specified subindex.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 94.

SubIndex Name Variable Type Default Value
1011h Subindex 0 Number of Entries UNSIGNED8 calc
1011h Subindex 1 All Parameters UNSIGNED32 1
1011h Subindex 2 Communication Parameters (1000h-1FFFh) UNSIGNED32 1
1011h Subindex 3 Application Parameters (2000h-27FFh) UNSIGNED32 1
1011h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 0 to 0x7F Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1011h Subindex 1 - All Parameters

This restores all Parameters to default (Factory Setting), the values are loaded directly but they are set valid until the

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1011h Subindex 2 - Communication Parameters (1000h-1FFFh)

This restores all Communication Parameters (1000-1FFF) to default (Factory Setting)

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1011h Subindex 3 - Application Parameters (2000h-27FFh)

This restores all Application Specific Parameters (2000-27FF) to default (Factory Setting)

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, RAM Formatting:  
Value: to Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1012h - COB-ID Time Stamp

COB-ID of the Time Stamp Object (TIME). If bit 31 is set the device consumes the Time Stamp message and if bit 30 is set the device produces the Time Stamp message. The meaning of the other bits is equal to the other communication objects.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 97.

Note: The bits 29 and 30 are not supported and must be 0.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: 0x80000100, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1014h - COB-ID EMCY

Error Broadcast function. COB-ID used for emergency message (Emergency Server).

Note: For more information see CiA Draft Standard 301, Version 4.02, page 98.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: $NODEID+0x00000080, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1016h - Consumer Heartbeat Time

The consumer heartbeat time defines the expected heartbeat cycle time and thus has to be higher than the corresponding producer heartbeat time configured on the device producing this heartbeat. Monitoring starts after the reception of the first heartbeat. If the consumer heartbeat time is 0 the corresponding entry is not used. The time has to be a multiple of 1ms.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 100.

SubIndex Name Variable Type Default Value
1016h Subindex 0 Number of Entries UNSIGNED8 1
1016h Subindex 1 Consumer Heartbeat Time (I/O Module) UNSIGNED32 0x004107D0
1016h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 1 to 2 Default, Error: 1, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1016h Subindex 1 - Consumer Heartbeat Time (I/O Module)

This contains the NodeId and the Heartbeat Time of the I/O Module (or Gateway). If the heartbeat time is equal to 0, no heartbeat is checked, and the bus-control mode is completely operational. If the heartbeat time is unequal to 0 then the heartbeat must be present in order to activate the Bus-Control Mode (see Par 200Ah Bit 5 - Activate Bus Setpoint for more info). If the heartbeat is lost and the Heartbeat Time is unequal to 0, then the pump sets the extern Off/Max/Min/On bits to 0, (exception, If Ext-Off was active the pump is turned off. If Ext-Max, Ext-Min or Ext-On was activated the pump returns to its previous state). The bits Par 200Ah Bit 5 - Activate Bus Setpoint and Par 200Ah Bit 6 - Activate Bus Control Mode are reset to 0. An Error is also triggered.

Note: The default value of NodeId (bit 16 to 23) is $NODEID+64. NodeId must not be equal to the NodeId of this device or any other subindex of Par 1016h - Consumer Heartbeat Time, and it must be in the range of 1 to 127.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Bit Bit equals Zero Bit equals One
0-15 Heartbeat Time (ms)
16-23 NodeId
24-31 Reserved (Always 0)
Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0 to 0x7FFFFF Default, Error: 0x004107D0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1017h - Producer Heartbeat Time

The producer heartbeat time defines the cycle time of the heartbeat. If the time is 0 it is not used. The time has to be a multiple of 1 msec.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 101.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 1000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

1018h - Identity Object

This object contains general information about the device.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 101.

SubIndex Name Variable Type Default Value
1018h Subindex 0 Number of Entries UNSIGNED8 4
1018h Subindex 1 Vendor Id UNSIGNED32 0x239
1018h Subindex 2 Product Code UNSIGNED32 0
1018h Subindex 3 Revision number UNSIGNED32 0
1018h Subindex 4 Serial number UNSIGNED32 0
1018h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 1 to 4 Default, Error: 4, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

1018h Subindex 1 - Vendor Id

contains a unique value allocated each manufacturer. Wilo devices will contin the number 0x239 ('WILO').

Variable Type: UNSIGNED32, ROM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0x239, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

1018h Subindex 2 - Product Code

identifies the manufacturer specific product code. Wilo products stores their Article Number In this subindex.

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

1018h Subindex 3 - Revision number

contains the revision number.

Bit 31-16 is the major revision number and Bit 15-0 the minor revision number. (Contains a CAN open revision number, see CANopen v4.02 p.101)

Variable Type: UNSIGNED32, ROM Formatting:  
Value: 0 to 0xFFFFFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

1018h Subindex 4 - Serial number

identifies a manufacturer specific serial number. Wilo devices stores their Serial Number here. The format is (decimal) a number followed by production year, week ('NNNNNYYWW').The Decimal number 90512 would mean number '9', produced Week 12, 2005.

Variable Type: UNSIGNED32, EEPROM Formatting: Number
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

1200h - Server SDO Parameter 1

The object contains the parameters for the SDOs for which the device is the server.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 103.

SubIndex Name Variable Type Default Value
1200h Subindex 0 Number of Entries UNSIGNED8 2
1200h Subindex 1 COB-ID Client -> Server UNSIGNED32 $NODEID+0x00000600
1200h Subindex 2 COB-ID Server -> Client UNSIGNED32 $NODEID+0x00000580
1200h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 2 to 2 Default, Error: 2, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1200h Subindex 1 - COB-ID Client -> Server

Variable Type: UNSIGNED32, ROM Formatting:  
Value: 0x00000600 to 0xBFFFFFFF Default, Error: $NODEID+0x00000600, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1200h Subindex 2 - COB-ID Server -> Client

Variable Type: UNSIGNED32, ROM Formatting:  
Value: 0x00000580 to 0xBFFFFFFF Default, Error: $NODEID+0x00000580, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1400h - Receive PDO Communication Parameter 1

A Wilo Device will have this Receive PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).

If a cyclic control of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 106.

SubIndex Name Variable Type Default Value
1400h Subindex 0 Number of Entries UNSIGNED8 2
1400h Subindex 1 COB-ID UNSIGNED32 $NODEID+0x40000200
1400h Subindex 2 Transmission Type UNSIGNED8 0xFE
1400h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 2 to 5 Default, Error: 2, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1400h Subindex 1 - COB-ID

Note: The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: $NODEID+0x40000200, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1400h Subindex 2 - Transmission Type

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 0xFE, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1600h - Receive PDO Mapping Parameter 1

A Wilo Device will have this Receive PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).

If a cyclic control of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 109.

SubIndex Name Variable Type Default Value
1600h Subindex 0 Number of Entries UNSIGNED8 3
1600h Subindex 1 Mapping Entry 1 UNSIGNED32 0x20080010
1600h Subindex 2 Mapping Entry 2 UNSIGNED32 0x20090008
1600h Subindex 3 Mapping Entry 3 UNSIGNED32 0x200A0008
1600h Subindex 4 Mapping Entry 4 UNSIGNED32 0x00000000
1600h Subindex 5 Mapping Entry 5 UNSIGNED32 0x00000000
1600h Subindex 6 Mapping Entry 6 UNSIGNED32 0x00000000
1600h Subindex 7 Mapping Entry 7 UNSIGNED32 0x00000000
1600h Subindex 8 Mapping Entry 8 UNSIGNED32 0x00000000
1600h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 3, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1600h Subindex 1 - Mapping Entry 1

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x20080010, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1600h Subindex 8 - Mapping Entry 8

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x00000000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h - Transmit PDO Communication Parameter 1

A Wilo Device will have this Transmit PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).

If a cyclic status of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 111.

SubIndex Name Variable Type Default Value
1800h Subindex 0 Number of Entries UNSIGNED8 5
1800h Subindex 1 COB-ID UNSIGNED32 $NODEID+0x40000180
1800h Subindex 2 Transmission Type UNSIGNED8 0xFE
1800h Subindex 3 Inhibit Time UNSIGNED16 500
1800h Subindex 4 Compatibility Entry UNSIGNED8 0
1800h Subindex 5 Event Timer UNSIGNED16 1000
1800h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 2 to 5 Default, Error: 5, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h Subindex 1 - COB-ID

Note: The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: $NODEID+0x40000180, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h Subindex 2 - Transmission Type

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 0xFE, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h Subindex 3 - Inhibit Time

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 500, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h Subindex 4 - Compatibility Entry

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1800h Subindex 5 - Event Timer

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 1000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h - Transmit PDO Communication Parameter 2

A Wilo Device will have this Transmit PDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).

If cyclic measure values of the pump is wanted, this is the preferred PDO. It is recommended to use the default configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 111.

SubIndex Name Variable Type Default Value
1801h Subindex 0 Number of Entries UNSIGNED8 5
1801h Subindex 1 COB-ID UNSIGNED32 $NODEID+0xC0000280
1801h Subindex 2 Transmission Type UNSIGNED8 0xFE
1801h Subindex 3 Inhibit Time UNSIGNED16 2000
1801h Subindex 4 Compatibility Entry UNSIGNED8 0
1801h Subindex 5 Event Timer UNSIGNED16 10000
1801h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 2 to 5 Default, Error: 5, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h Subindex 1 - COB-ID

Note: The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: $NODEID+0xC0000280, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h Subindex 2 - Transmission Type

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 0xFE, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h Subindex 3 - Inhibit Time

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 2000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h Subindex 4 - Compatibility Entry

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1801h Subindex 5 - Event Timer

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 10000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h - Transmit MPDO Communication Parameter 3

A Wilo Device will have this Transmit MPDO active by default, if this is not wanted it must be turned off manually and its wanted state can be stored to non-volatile memory using Par 1010h Sub 2 - Communication Parameters (1000h-1FFFh).

This PDO cannot be configured as a normal PDO, It is only possible to use this PDO as an MPDO. If cyclic measure values of the pump is wanted, this is the preferred PDO. Any Value can be added or removed from the Scanner list in Par 1FA0h - Object Scanner List..

Note: For more information see CiA Draft Standard 301, Version 4.02, page 111.

SubIndex Name Variable Type Default Value
1802h Subindex 0 Number of Entries UNSIGNED8 5
1802h Subindex 1 COB-ID UNSIGNED32 $NODEID+0x40000380
1802h Subindex 2 Transmission Type UNSIGNED8 0xFE
1802h Subindex 3 Inhibit Time UNSIGNED16 1000
1802h Subindex 4 Compatibility Entry UNSIGNED8 0
1802h Subindex 5 Event Timer UNSIGNED16 60000
1802h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 2 to 5 Default, Error: 5, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h Subindex 1 - COB-ID

Note: The functions behind the bits 29 and 30 are not supported so bit 29 must be 0 and the bit 30 must be 1.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 1 to 0xFFFFFFFF Default, Error: $NODEID+0x40000380, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h Subindex 2 - Transmission Type

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 0xFE, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h Subindex 3 - Inhibit Time

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 1000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h Subindex 4 - Compatibility Entry

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1802h Subindex 5 - Event Timer

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting:  
Value: 0 to 0xFFFF Default, Error: 60000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A00h - Transmit PDO Mapping Parameter 1

A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 112.

SubIndex Name Variable Type Default Value
1A00h Subindex 0 Number of Entries UNSIGNED8 7
1A00h Subindex 1 Mapping Entry 1 UNSIGNED32 0x20400010
1A00h Subindex 2 Mapping Entry 2 UNSIGNED32 0x20410008
1A00h Subindex 3 Mapping Entry 3 UNSIGNED32 0x20420008
1A00h Subindex 4 Mapping Entry 4 UNSIGNED32 0x20500008
1A00h Subindex 5 Mapping Entry 5 UNSIGNED32 0x20520008
1A00h Subindex 6 Mapping Entry 6 UNSIGNED32 0x20540008
1A00h Subindex 7 Mapping Entry 7 UNSIGNED32 0x20560008
1A00h Subindex 8 Mapping Entry 8 UNSIGNED32 0x00000000
1A00h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 7, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A00h Subindex 1 - Mapping Entry 1

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x20400010, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A00h Subindex 8 - Mapping Entry 8

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x00000000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A01h - Transmit PDO Mapping Parameter 2

A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 112.

SubIndex Name Variable Type Default Value
1A01h Subindex 0 Number of Entries UNSIGNED8 3
1A01h Subindex 1 Mapping Entry 1 UNSIGNED32 0x20900020
1A01h Subindex 2 Mapping Entry 2 UNSIGNED32 0x208B0010
1A01h Subindex 3 Mapping Entry 3 UNSIGNED32 0x20A00010
1A01h Subindex 4 Mapping Entry 4 UNSIGNED32 0x00000000
1A01h Subindex 5 Mapping Entry 5 UNSIGNED32 0x00000000
1A01h Subindex 6 Mapping Entry 6 UNSIGNED32 0x00000000
1A01h Subindex 7 Mapping Entry 7 UNSIGNED32 0x00000000
1A01h Subindex 8 Mapping Entry 8 UNSIGNED32 0x00000000
1A01h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 3, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A01h Subindex 1 - Mapping Entry 1

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x20900020, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A01h Subindex 8 - Mapping Entry 8

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x00000000, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1A02h - Transmit MPDO Mapping Parameter 3

A Wilo Device will have this Transmit PDO preconfigured, It is recommended to use this pre configured configuration.

Note: For more information see CiA Draft Standard 301, Version 4.02, page 112.

SubIndex Name Variable Type Default Value
1A02h Subindex 0 Number of Entries UNSIGNED8 0xFE
1A02h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 0xFE, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1FA0h - Object Scanner List

It contains the mapping parameter for the MPDOs (configured with Par 1802h - Transmit MPDO Communication Parameter 3 and Par 1A02h - Transmit MPDO Mapping Parameter 3) the device is able to transmit. Sub-index 0 contains the number of mapped objects. All further entries define the data by its index, sub-index and length

Note: For more information see CiA Draft Standard 301, Version 4.02, page 128.

SubIndex Name Variable Type Default Value
1FA0h Subindex 0 Number of Entries UNSIGNED8 8
1FA0h Subindex 1 Scanner Entry 1 UNSIGNED32 0x01209200
1FA0h Subindex 2 Scanner Entry 2 UNSIGNED32 0x01208700
1FA0h Subindex 3 Scanner Entry 3 UNSIGNED32 0x01210100
1FA0h Subindex 4 Scanner Entry 4 UNSIGNED32 0x01211300
1FA0h Subindex 5 Scanner Entry 5 UNSIGNED32 0x00000000
1FA0h Subindex 6 Scanner Entry 6 UNSIGNED32 0x00000000
1FA0h Subindex 7 Scanner Entry 7 UNSIGNED32 0x00000000
1FA0h Subindex 8 Scanner Entry 8 UNSIGNED32 0x00000000
1FA0h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, ROM Formatting:  
Value: 0x00 to 0xFF Default, Error: 8, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.

1FA0h Subindex 1 - Scanner Entry 1

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting:  
Value: 0x00000000 to 0xFFFFFFFF Default, Error: 0x01209200, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This Pump.


Section Control

2000h - Pump Setpoint

This Parameter sets the active working point of the pump. The resolution is in 0.01 Percent which means that the value 10000 corresponds to 100%. 100% represents the max setpoint (depending on Control Mode, Max Pressure, Max Speed, etc.) and 0% represents the setpoint 0 (not depending on control Mode).

If a value is written that is lower than the specified pump min value (depending on Control Mode) it is limited to the min value and the Par 2050h Bit 2 - Setpoint out of Range is set. The pump does not turn off if the value 0 is written.

The setpoint is saved internally on power off. If the pump is restarted or rebooted the last value is loaded automatically.

Usage: This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to change the Setpoint from other sources. If an automated source is to set Values, then use Par 2008h - Bus Setpoint instead of this Parameter.

Note: This Parameter is write only, in order to read back the setpoint that is being processed by the pump, read Par 2048h - Wanted Setpoint.

Dependency: This Parameter can change meaning if Par 2041h - System Control Mode changes.

Dependency: This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "1".

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: SIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 10000 Default, Error: 5000, n/a
Permission: wo PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2001h - Pump Control Mode

This Parameter sets the active control mode of the pump. It is basically the same as the Par 2009h - Bus Control Mode. If a Control Mode is to be set in the pump, this parameter should be used. This Parameter has no constant min and max values, instead it allows only the supported Control Modes to be written to This Parameter. If a value is written, that is not supported, a min, max or other suitable error will be generated by the pump and the last valid value will be kept.

If CONST_SPEED mode is set in a DP System, both pumps run syncronously. CONST_SPEED mode is not supported by this parameter if the active pump is in a MP system.

The control mode is saved internally on power off. If the pump is restarted or rebooted the last value is loaded automatically.

Usage: This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to change the Control Mode from other sources. If an automated source is to set values, then use Par 2009h - Bus Control Mode instead of this Parameter. This value does not affect the value of Par 2000h - Pump Setpoint (or Par 2008h - Bus Setpoint) and Par 2048h - Wanted Setpoint (if they already were at 50% they stay at 50% after changing this Parameter).

Note: This Parameter is write only, in order to read back the chosen setpoint for the pump, read Par 2049h - Wanted Control Mode.

Dependency: This Parameter is disabled, if the Par 200Ah Bit 6 - Activate Bus Control Mode is set to "1".

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Dependency: This Parameter disables Par 208Bh - Estimated Pressure (System), if it is set to "CONST_CONTROL (PID)".

Value Description
0 CONST_SPEED (n-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
11 TEMP_VARIABLE (dp-c=f(T))
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 12 Default, Error: 5, n/a
Permission: wo PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2002h - Pump Command

This Parameter controls the running mode of the pump.

Usage: This value should not be automatically written, it should only be written if a change is required (a user manually changes the setpoint on a monitor or alike) otherwise it will take priority over other control methods, and would make it impossible to turn the pump on or off from other sources. If an automated source is to set values, then use Par 200Ah - Bus Command instead of this Parameter.

Dependency: This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "1".

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Bit Bit equals Zero Bit equals One
0 Pump Off Pump On
Variable Type: UNSIGNED8, EEPROM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0x01, n/a
Permission: wo PDO: no

In the case of a Single Pump,
In the case of a Double Pump - Master,

2002h Bit 0 - Pump On/Off

This Bit turns the pump on or off. On means that the pump is pumping and Off means that the pump is not pumping. It is not possible to completely turn off the pump, the pump is always in standby mode.

Note: The on off setting is saved internally on power off, this parameter becomes this saved value upon restart or reboot.

Dependency: This Bit has the same priority as Par 200Ah Bit 0 - Pump On/Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.

Dependency: This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.

Dependency: This Bit has lower priority than Par 200Ah Bit 4 - Extern On.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2008h - Bus Setpoint

This Parameter sets the active working point of the pump.

Usage: This value should only be used if a source continuosly sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2000h - Pump Setpoint.

Note: If the setpoint is accompanied with a control mode (PDO), and the control mode is invalid, only the setpoint will be accepted and it would then depend on the previously selected control mode.

Note: This Parameter is write only, in order to read back the setpoint that is being processed by the pump, read Par 2048h - Wanted Setpoint.

Note: All percentages lower than the current min value (depending on Control Mode) are accepted, but limits the value to the min value. This activates the Par 2050h Bit 2 - Setpoint out of Range. The pump does not turn off if the value 0 is written to This Parameter.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: In the case of a DP or multipump where one or more pumps are set to Off, Max, Min or On, the other (DP), or one of the others (MP), still regulates with the chosen setpoint (This Parameter). This means that an external regulation unit can set specific pumps to Off, Max, Min or On (with specified fixed speed) and still regulate the last pump externally.

Dependency: This Parameter can change meaning if Par 2041h - System Control Mode changes.

Dependency: This Parameter is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "0".

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: SIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 10000 Default, Error: 5000, n/a
Permission: wo PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2009h - Bus Control Mode

This Parameter is basically the same as the Par 2001h - Pump Control Mode. The difference is that this parameter is written by a I/O-Module and it can have a higher priority (set by Par 200Ah Bit 6 - Activate Bus Control Mode) than its counterpart. It sets the active control mode of the pump.

Usage: This value should only be used if a source continuosly sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2001h - Pump Control Mode.

Note: This Parameter is write only, in order to read back the chosen setpoint for the pump, read Par 2049h - Wanted Control Mode.

Note: This Parameter has no constant min and max values, instead it allows only the supported Control Modes to be written to This Parameter. If a value is written, that is not supported, a min, max or other suitable error will be generated by the pump.

Note: This Parameter is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: If CONST_SPEED mode is set in a DP System, both pumps run syncronously.

Note: CONST_SPEED mode is only supported by this parameter if the active pump is in a MP system. The MP CONST_SPEED mode is very different from the DP speed mode.

Dependency: This Parameter is disabled, if the Par 200Ah Bit 6 - Activate Bus Control Mode is set to "0".

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Dependency: This Parameter disables Par 208Bh - Estimated Pressure (System), if it is set to "CONST_CONTROL (PID)".

Value Description
0 CONST_SPEED (n-c)
5 CONST_DIFFPRESS (dp-c)
6 VAR_DIFFPRESS (dp-v)
11 TEMP_VARIABLE (dp-c=f(T))
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 12 Default, Error: 5, n/a
Permission: wo PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

200Ah - Bus Command

Note: This Parameter is write only, in order to read back the chosen setpoint for the pump, some of the values can be read in Par 204Ah - Wanted Command.

Note: This Parameter is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: The activation bits are always evaluated first, so this byte can contain an combination of different values.

Note: This Parameter is deactivated if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.

Example: If Par 200Ah Bit 2 - Extern Max is set in an MP system, then all pumps would run at Maximum Speed. If Par 2021h Sub 2 - Extern Off (Slave 1) is set at the same time, all pumps would run at Maximum Speed, but Slave 2, since Extern Off has higher Priority than Extern Max, would be turned off.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Bit Bit equals Zero Bit equals One
0 Pump Off Pump On
1 No Influence Pump Off Override
2 No Influence Pump Max Override
3 No Influence Pump Min Override
4 No Influence Pump On Override
5 Activate P2000 Activate P2008
6 Activate P2001 Activate P2009
Variable Type: UNSIGNED8, EEPROM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0x01, n/a
Permission: wo PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

200Ah Bit 0 - Pump On/Off

This Bit turns the pump on or off. On means that the pump is pumping and Off means that the pump is not pumping. It is not possible to completely turn off the pump, the pump is always in standby mode.

Usage: This value should only be used if a source continuosly sends values (a regulation unit, a 0-10V conversion unit or similar). If only a new value is to be written, then use Par 2002h Bit 0 - Pump On/Off.

Note: The effective value in the pump is saved with power off (non-volatile).

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Dependency: This Bit has the same priority as Par 2002h Bit 0 - Pump On/Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.

Dependency: This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.

Dependency: This Bit has lower priority than Par 200Ah Bit 4 - Extern On.

Dependency: This Bit has partially lower priority than all subitems of Par 2021h - Extern Off (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2023h - Extern Max (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2025h - Extern Min (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2027h - Extern Fixed On (DP/MP).

Dependency: This Bit is disabled, if the Par 200Ah Bit 5 - Activate Bus Setpoint is set to "0".

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

200Ah Bit 1 - Extern Off

This Bit turns the pump off, disregarding the previous setting (also see priority dependencies below).

Usage: This value should only be used if a source continuosly sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by setting Par 2002h Bit 0 - Pump On/Off to 0.

Note: This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: See Par 200Ah - Bus Command for an Priority example.

Note: It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.

Note: If this variable is set, it is also displayed in the Old IR-Monitor.

Dependency: This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.

Dependency: This Bit has higher priority than Par 200Ah Bit 2 - Extern Max.

Dependency: This Bit has higher priority than Par 200Ah Bit 3 - Extern Min.

Dependency: This Bit has higher priority than Par 200Ah Bit 4 - Extern On.

Dependency: This Bit has higher priority than all subitems of Par 2021h - Extern Off (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2023h - Extern Max (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2025h - Extern Min (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2027h - Extern Fixed On (DP/MP).

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

200Ah Bit 2 - Extern Max

This Bit makes the pump run at maximum speed, disregarding the previous setting (also see priority dependencies below).

Usage: This value should only be used if a source continuosly sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by first setting the Par 2000h - Pump Setpoint to 100% and then Par 2001h - Pump Control Mode to Speed mode. To disable this mimic, first write the old value to Par 2001h - Pump Control Mode then the old value to Par 2000h - Pump Setpoint.

Note: This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: See Par 200Ah - Bus Command for an Priority example.

Note: It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.

Dependency: This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.

Dependency: This Bit has higher priority than Par 200Ah Bit 3 - Extern Min.

Dependency: This Bit has higher priority than Par 200Ah Bit 4 - Extern On.

Dependency: This Bit has partially lower priority than all subitems of Par 2021h - Extern Off (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2023h - Extern Max (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2025h - Extern Min (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2027h - Extern Fixed On (DP/MP).

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

200Ah Bit 3 - Extern Min

This Bit makes the pump run at minimum speed, disregarding the previous setting (also see priority dependencies below).

Usage: This value should only be used if a source continuosly sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by first setting the Par 2000h - Pump Setpoint to 0% and then Par 2001h - Pump Control Mode to Speed mode. To disable this mimic, first write the old value to Par 2001h - Pump Control Mode then the old value to Par 2000h - Pump Setpoint.

Note: This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: See Par 200Ah - Bus Command for an Priority example.

Note: The Extern Min function reduces the speed of the pump to a level where a minimal function is guaranteed. It does not always correspond to the min speed value.

Note: It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.

Dependency: This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.

Dependency: This Bit has higher priority than Par 200Ah Bit 4 - Extern On.

Dependency: This Bit has partially lower priority than all subitems of Par 2021h - Extern Off (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2023h - Extern Max (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2025h - Extern Min (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2027h - Extern Fixed On (DP/MP).

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

200Ah Bit 4 - Extern On

This Bit turns the pump on, disregarding the previous setting (also see priority dependencies below).

Usage: This value should only be used if a source continuosly sends values (a regulation unit). If this functionality is required, without having a regulation source then you can mimic this Parameter by setting Par 2002h Bit 0 - Pump On/Off to 1.

Note: This Subindex must not be saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Master device.

Note: See Par 200Ah - Bus Command for an Priority example.

Note: It is only possible to write or modify this bit if an I/O Module (or gateway, depending on Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module)) is sending Heartbeats on the configured address. If this Heartbeat is lost this Parameter is set to 0.

Dependency: This Bit has higher priority than Par 200Ah Bit 0 - Pump On/Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 1 - Extern Off.

Dependency: This Bit has lower priority than Par 200Ah Bit 2 - Extern Max.

Dependency: This Bit has lower priority than Par 200Ah Bit 3 - Extern Min.

Dependency: This Bit has partially lower priority than all subitems of Par 2021h - Extern Off (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2023h - Extern Max (DP/MP).

Dependency: This Bit has partially lower priority than all subitems of Par 2025h - Extern Min (DP/MP).

Dependency: This Bit has higher priority than all subitems of Par 2027h - Extern Fixed On (DP/MP).

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

200Ah Bit 5 - Activate Bus Setpoint

This Bit activates the setpoint and the on off setting over the bus.

Note: This Subindex is not saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Bus Regulation device.

Note: To read the status of this bit, use Par 2056h Bit 2 - Bus Setpoint Active.

Note: This Subindex is disabled if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Dependency: This Bit disables Par 2000h - Pump Setpoint, if it is set to "1".

Dependency: This Bit disables Par 2008h - Bus Setpoint, if it is set to "0".

Dependency: This Bit disables Par 2002h Bit 0 - Pump On/Off, if it is set to "1".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

200Ah Bit 6 - Activate Bus Control Mode

This Bit activates the Control Mode over the bus.

Note: This Subindex is not saved with power off. If the pump resets and boots without the connected unit, it should be accessible over normal parametering.

Note: This Subindex is reserved for I/O-Module or Bus communication, it should not be used by a Gateway or other Bus Regulation device.

Note: To read the status of this bit, use Par 2056h Bit 3 - Bus Control Mode Active.

Note: This Subindex is disabled if Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is activated and no corresponding heartbeat is present on the bus.

Dependency: CAN write access to This Bit is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Dependency: This Bit disables Par 2001h - Pump Control Mode, if it is set to "1".

Dependency: This Bit disables Par 2009h - Bus Control Mode, if it is set to "0".

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.


Section Status

2040h - System Actual Capacity

This Parameter contains the actual value of the pump, at which it works in this moment, in percent. This value is usually very close to the wanted setpoint ( Par 2048h - Wanted Setpoint). This value is relative to the actual Control Mode ( Par 2041h - System Control Mode). 100% represents the max value for the chosen control mode (as described in Par 2000h - Pump Setpoint).

Note: In the case of a Double- or Multi-Pump System, This Parameter is a System Parameter, it always represents data for the complete Double- or Multi-Pump System.

Note: In the case of a DP or MP System it contains the speed of the active running pump(s), and if CONST_SPEED, together with two pumps running at a different speeds, it contains the Error Value.

Dependency: This Parameter can change meaning if Par 2041h - System Control Mode changes.

Variable Type: SIGNED16, RAM Formatting: 0.01 Percent
Value: 0x8000 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2041h - System Control Mode

This Parameter contains the current active regulation mode. see Pump Control Mode for the regulation modes. For a list of modes see Par 2001h - Pump Control Mode.

Note: The effective values in the pump are saved with power off (non-volatile).

Note: the value must represent one of the supported control modes.

Note: In the case of a Double- or Multi-Pump System, This Parameter is a System Parameter, it always represents data for the complete Double- or Multi-Pump System.

Dependency: This Parameter can change if Par 2049h - Wanted Control Mode changes.

Variable Type: UNSIGNED8, RAM Formatting: Select
Value: 0 to 0xFF Default, Error: 0, 0xFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2042h - System Command

This Parameter contains actual values that has been acceped by the pump, or in the case of an DP/MP System, all pumps. This means that in an EP Pump only one bit can be active at any one time. In a DP or MP Pump more bits can be active if the members have different bits set.

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2042h Bit 0 - Pump On/Off

This Bit shows if the pump (or at least one of the pumps from the System) is turned on with the on/off bit (no extern values). This means that if at least one pump of the system is pumping without having the bit extern max, extern min or extern on set, this bit is set.

Note: If this bit is 0, some pumps can still run! To see if all pumps are stopped please use Par 2052h Bit 1 - Pump is Operating.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2042h Bit 1 - Extern Off

This Bit shows if the pump has been turned off with an Extern Off function. This bit is active when one or more of all Extern Off functions in the pump is active. It does not activate if only the pump is turned off with the Pump On/Off parameter.

This bit contains the value '1' if at least one pump in the DP or MP System is stopped by Extern Off.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2042h Bit 2 - Extern Max

This Bit shows if the pump has been set to run at maximum speed with an Extern Max function. This bit is active when one or more of all Extern Max functions in the pump is active. It does not activate if only the pump is set to max with the normal setpoint parameter.

This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern Max.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2042h Bit 3 - Extern Min

This Bit shows if the pump has been set to run at minimum speed with an Extern Min function. This bit is active when one or more of all Extern Min functions in the pump is active. It does not activate if only the pump is set to min with the normal setpoint parameter.

This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern Min.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2042h Bit 4 - Extern On

This Bit shows if the pump has been turned on with an Extern On function. This bit is active when one or more of all Extern On functions in the pump is active. It does not activate if only the pump is turned on with the Pump On/Off parameter.

This bit contains the value '1' if at least one pump in the DP or MP System is running in Extern On.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2048h - Wanted Setpoint

This Parameter contains the last written setpoint. This is the readback parameter of Par 2000h - Pump Setpoint, Par 2008h - Bus Setpoint and setpoint from the Pump Menu.

Note: This value is the same value that is displayed in the pump display.

Dependency: This Parameter can change meaning if Par 2041h - System Control Mode changes.

Variable Type: SIGNED16, RAM Formatting: 0.01 Percent
Value: 0x8000 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2049h - Wanted Control Mode

This Parameter contains the last written Control Mode. This is the readback parameter of Par 2001h - Pump Control Mode, Par 2009h - Bus Control Mode and the Control Mode item from the Pump Display.

Dependency: This Parameter can change if Par 2001h - Pump Control Mode changes.

Dependency: This Parameter can change if Par 2009h - Bus Control Mode changes.

Dependency: This Parameter can change source if Par 200Ah Bit 5 - Activate Bus Setpoint changes.

Dependency: This Parameter can change source if Par 200Ah Bit 6 - Activate Bus Control Mode changes.

Variable Type: UNSIGNED8, RAM Formatting: Select
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

204Ah - Wanted Command

This Parameter contains the last written Pump Command. This is the readback parameter of Par 2002h - Pump Command, Par 200Ah - Bus Command and the On/Off item from the Pump Display.

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

204Ah Bit 0 - Pump On/Off

This Bit shows if the pump (or System) is turned on or off. On means that at least one pump of the system is pumping without having the bit extern max/min or on set. Off means that the pump is not pumping.

Note: If the pump is set to On, but Extern Off is active this Parameter would show On.

Note: Pumps can be running even if this Parameter shows Off!

Note: This Subindex contains the value '1' if the pump on/off command has been set to On.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

204Ah Bit 1 - Extern Off

This Bit shows if the pump has been turned off with an Extern Off function.

Note: This Subindex contains the value '1' if at least one extern off function has been activated.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

204Ah Bit 2 - Extern Max

This Bit shows if the pump has been set to run at maximum speed with an Extern Max function.

Note: This Subindex contains the value '1' if at least one extern max function has been activated.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

204Ah Bit 3 - Extern Min

This Bit shows if the pump has been set to run at minimum speed with an Extern Min function.

Note: This Subindex contains the value '1' if at least one extern min function has been activated.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

204Ah Bit 4 - Extern On

This Bit shows if the pump has been turned on with an Extern On function.

Note: This Subindex contains the value '1' if at least one extern on function has been activated.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2050h - Controller Status (System)

This parameter returns regulation information from the Pump or System.

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2050h Bit 0 - Lower Regulation Limit

This Bit contains status over the Lower Regulation Limit (pump is running at min speed).

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps and its min and max values, so this bit is superfluous.

Note: This Subindex is '1' if the DP or MP System is operating at the lowest possible operation point.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 1 - Upper Regulation Limit

This Bit contains status over the Upper Regulation Limit (pump is running at max speed, or max power).

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps and its min and max values, so this bit is superfluous.

Note: This Subindex is '1' if the DP or MP System is operating with the highest possible speed or effect.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 2 - Setpoint out of Range

This Bit contains '1' if the last setpoint was out of range (if setpoint was smaller than min for the selected control mode).

Note: Since the Min value will changes dependent on Pump type and capacity, this parameter adapts to EP, DP-MA/MP-MA changes automatically.

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps, so this bit is superfluous.

Note: DP-MP, This Subindex is '1' if the setpoint (in the Master) is set to a value below the specified min-value (for the current operation mode).

Dependency: This Bit can change if Par 2041h - System Control Mode changes.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 3 - Setpoint Difference (>10%)

This Bit contains if the setpoint and Actual Value difference is larger than 10% (>+-10%).

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps. Extern Multipump regulators will know the current speed of the slave pumps, so this bit is superfluous.

Note: DP-MP, This Subindex is '1' if the setpoint (in the Master) differs with more than 10% from the Actual Value.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 4 - Q not Computable

This Bit contains if Q is not computable.

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.

Note: This Subindex is '1' if the DP or MP System is in a position where it cannot calculate the flow.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 5 - H not Computable

This Bit contains if H is not computable.

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.

Note: This Subindex is '1' if the DP or MP System is in a position where it cannot calculate the pressure.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2050h Bit 6 - Auto Night Active

This Bit contains if Auto Night is active or not.

Note: In a Double or Multi Pump System, This value can only be read from the Master, and it contains the value from the System, not single pumps.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h - Operation Status (System)

This Parameter describes the current Operation Status, if the pump is ready, if error is present and so on.

Note: This Parameter can be read for each slave as well, this is possible from Par 2058h - Ready for Operation (DP/MP), Par 205Ah - Pump is Operating (DP/MP), Par 205Ch - Service Required (DP/MP), Par 205Eh - Warning Present (DP/MP) and Par 2060h - Error Present (DP/MP).

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2052h Bit 0 - Ready for Operation

This Bit contains the Ready for Operation status for the Single Pump or in the case of a DP or MP System, for the Complete System. If at least one Pump is Ready for Operation in the System, this bit is set. Ready for Operation means that the pump will start as soon as it is turned on (power, no error, not disabled and no extern off).

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h Bit 1 - Pump is Operating

This Bit contains if the pump is operating. In the case of a DP or MP System, this bit is set if at least one Pump is operating. Operating means that the pump rotates.

Note: A pumpkick also makes this flag turn on.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h Bit 2 - Service Required

This Bit contains a '1' if Service is required for this pump or in the case of a DP or MP System, If at least one Pump requires Service. The service required information can be set together with a warning or an error. If it is set alone, it is usually an indication that it is time for service (parts exchange or similar). If it is set together with a warning or an error is indicates that this warning or error can only be resetted by someone at the pump, and not remotely or by itself.

Note: This Subindex is set together with some errors (See Wilo LON spec EBA_8120_10) and it can be set on its own. To see why it was set, a Service Register ( Par 20CBh - Current Service Message) can be read.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h Bit 3 - Warning Present

This Bit contains a '1' if a Warning is present in this pump or in the case of a DP or MP System, If at least one Pump has a Warning present. A warning means that something unwanted has happened but the motor still runs.

Note: Also see Par 2207h - HV/AC System Error Detection.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h Bit 4 - Error Present

This Bit contains a '1' if an Error is present in this pump or in the case of a DP or MP System, If at least one Pump has an Error present. An Error means that something unwanted has happened and the motor has turned off.

Note: An Error is sent when it occurs.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2052h Bit 5 - Final Error

This Bit contains a '1' if the Final Error Status has been reached (error is present in this pump or DP/MP System).

Note: A Final Error is usually sent when the sixth Error occurs. Also see Par 2207h - HV/AC System Error Detection.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2054h - Bus Status

This parameter describes what protocols and protocol modes are active.

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2054h Bit 0 - Bus Connected

This Bit is '1' if CAN is Connected (IF-CAN inserted and heartbeat on bus present)

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2054h Bit 1 - Module Auto Safety Active

This Bit is '1' if the Par 1016h Sub 1 - Consumer Heartbeat Time (I/O Module) is set to the default value (I/O Module Safety function is turned on and the address is set to the correct offset). It is basically a status flag to see if the heartbeat check is activated and unchanged, it is used by regulation units to see if they can pair up with this pump.

Note: A bit for the I/O-Module, so that it recognices if it is allowed to engage a connection to this pump.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2054h Bit 2 - Wink Service

If the menuitem "ID" is activated this bit is set to 1 for x seconds.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2054h Bit 3 - External Sensor Active

This Bit is set if an external sensor is used in the regulation loop. This Sensor can be connected over LON or CAN.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2054h Bit 5 - Module Auto Safety In Use

This Bit is set if a heartbeat is present on the address specified in P#1016,1. It used to see if the active regulation is activated (possible to set B#200A bits 1 through 6).

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h - Control Status

This Parameter returns control status information. All sources that can override the bus are listed here. If one of them temporarily or permamently takes control the corresponding bit is set high.

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2056h Bit 0 - LON/PLR Controlled

This Bit is '1' if LON/PLR is Connected (IF-LON/PLR inserted, the first message has been received and no timeout). This means that it is not possible to change values locally.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 1 - Bus Clamps Active

If the Gateway or I/O-Module has activated one of the parameters Par 200Ah Bit 1 - Extern Off to Par 200Ah Bit 4 - Extern On then this bit is set. It means that extern clamps are affecting the system so it might not behave as expected.

Note: In the case of an DP or MP Pump, this bit is set if at least one of the pumps behave as described above.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 2 - Bus Setpoint Active

If the Gateway or I/O-Module has activated the parameter Par 200Ah Bit 5 - Activate Bus Setpoint then this bit is set. It means that part of the Regulation control has been activated and that some control values might not possible to change.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 3 - Bus Control Mode Active

If the Gateway or I/O-Module has activated the parameter Par 200Ah Bit 6 - Activate Bus Control Mode then this bit is set. It means that part of the Regulation control has been activated and that some control values might not possible to change.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 4 - Local Operation Active

If the IR-Monitor or IR-Modul has activated the Local Operation mode (local access only), then this Parameter is set.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 5 - Pump Clamps Active

If one or more of the local Clamps (on the module itself or directly on an inserted IF-Module) on the Pump has been activated, this bit is set. It means that some control values might not possible to change. The relays (SBM, SSM) are no clamps and are not signalled here.

Note: In the case of an DP or MP Pump, this bit is set if at least one of the pumps behave as described above.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2056h Bit 6 - External Setpoint Active

This Bit is set if the Par 2235h - 0-10V Activate is set and the Master uses this external value as a setpoint value.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of the System Master.

2056h Bit 7 - Internally Controlled

This Bit is set if the pump internally sets values. Pump Kick and Auto Night Mode Modifies this bit, it is also set if an Error is active, that affects the operation of the pump. Another possibility is that the Interrupted Operation mode is active.

Note: Interrupted Operation: (EP/DP-SL/MP-SL, for this pump only) (DP-MA/MP-MA, The master can only enter the Int. Op. Mode if the sensor is broken or detached (E40, E42). An E52 will not bring the master or the system in an Interrupter Operation mode. This bit is thus only set if the system has lost its sensor, i.e. all pumps in this system is operating in Int. Op. Mode. If the slave is disconnected, 'E52', then the master cannot safely say that the slave is in Int. Op Mode therefore it should not report this, for more information see the E52-Description)

Note: In the case of an DP or MP Pump, this bit is set if at least one of the pumps behave as described above.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This System.

2058h - Ready for Operation (DP/MP)

This Parameter describes the current Operation Status, if the pump is ready, rotating, error is present and so on.

Bit Bit equals Zero Bit equals One
0 no Ready for Operation (Master) Ready for Operation (Master)
1 no Ready for Operation (Slave 1) Ready for Operation (Slave 1)
2 no Ready for Operation (Slave 2) Ready for Operation (Slave 2)
3 no Ready for Operation (Slave 3) Ready for Operation (Slave 3)
4 no Ready for Operation (Slave 4) Ready for Operation (Slave 4)
5 no Ready for Operation (Slave 5) Ready for Operation (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

205Ah - Pump is Operating (DP/MP)

Bit Bit equals Zero Bit equals One
0 no Pump is Operating (Master) Pump is Operating (Master)
1 no Pump is Operating (Slave 1) Pump is Operating (Slave 1)
2 no Pump is Operating (Slave 2) Pump is Operating (Slave 2)
3 no Pump is Operating (Slave 3) Pump is Operating (Slave 3)
4 no Pump is Operating (Slave 4) Pump is Operating (Slave 4)
5 no Pump is Operating (Slave 5) Pump is Operating (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

205Ch - Service Required (DP/MP)

This Parameter contains if the pump (or slave pump) needs service. This can be as a result of an error, for example if the pump is blocked (the part that is blocking the motor must be removed) or as a preemtive error notification. The preemptive notification can for example be "time to change bearing". See Par 20CBh - Current Service Message for more information (If this Parameter is not present then these bits are set with errors only).

Bit Bit equals Zero Bit equals One
0 no Service Required (Master) Service Required (Master)
1 no Service Required (Slave 1) Service Required (Slave 1)
2 no Service Required (Slave 2) Service Required (Slave 2)
3 no Service Required (Slave 3) Service Required (Slave 3)
4 no Service Required (Slave 4) Service Required (Slave 4)
5 no Service Required (Slave 5) Service Required (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

205Eh - Warning Present (DP/MP)

Bit Bit equals Zero Bit equals One
0 no Warning Present (Master) Warning Present (Master)
1 no Warning Present (Slave 1) Warning Present (Slave 1)
2 no Warning Present (Slave 2) Warning Present (Slave 2)
3 no Warning Present (Slave 3) Warning Present (Slave 3)
4 no Warning Present (Slave 4) Warning Present (Slave 4)
5 no Warning Present (Slave 5) Warning Present (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

2060h - Error Present (DP/MP)

Bit Bit equals Zero Bit equals One
0 no Error Present (Master) Error Present (Master)
1 no Error Present (Slave 1) Error Present (Slave 1)
2 no Error Present (Slave 2) Error Present (Slave 2)
3 no Error Present (Slave 3) Error Present (Slave 3)
4 no Error Present (Slave 4) Error Present (Slave 4)
5 no Error Present (Slave 5) Error Present (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

2062h - Final Error Present (DP/MP)

This Subindex contains the Final Error Present information of the Master in a DP or MP System.

Bit Bit equals Zero Bit equals One
0 no Final Error Present (Master) Final Error Present (Master)
1 no Final Error Present (Slave 1) Final Error Present (Slave 1)
2 no Final Error Present (Slave 2) Final Error Present (Slave 2)
3 no Final Error Present (Slave 3) Final Error Present (Slave 3)
4 no Final Error Present (Slave 4) Final Error Present (Slave 4)
5 no Final Error Present (Slave 5) Final Error Present (Slave 5)
Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

2064h - Rotating Direction (DP/MP)

This Subindex contains the Rotating Direction of all pumps in this system. This is the direction that the motor it rotating, that is if you stand behind the motor (where you see the ventilator blades of the motor).

Bit Bit equals Zero Bit equals One
0 Rotating Direction (Master) Right Left
1 Rotating Direction (Slave 1) Right Left
2 Rotating Direction (Slave 2) Right Left
3 Rotating Direction (Slave 3) Right Left
4 Rotating Direction (Slave 4) Right Left
5 Rotating Direction (Slave 5) Right Left
Variable Type: UNSIGNED8, RAM Formatting: Bit
Value: 0 to 1 Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump,
In the case of a Double Pump - Master,

206Eh - Number of DP/MP Pumps

This parameter reflects the number of pumps of the system that this pump is part of. If the pump is a Single Pump then it contains the value 1. If the pump is a Double Pump it contains the value 2. If it is a Multipump then it contains a value between 2 and 6. If at any time a new pump is connected to the system This Parameter increases. If at any time this pump works alone, this value will be 1.

Note: This Parameter changes it values to or from 0 and 1 automatically. In order to change This Parameter from a value higher than 1 to another value higher than 1, you have to write 0 to This Parameter (an Ident change force) or go through an ident change (MA-MA blinking has been confirmed). A factory reset does not reset this parameter!

Note: When this Parameter changes from a higher value than 1 to another value higher than 1, a Configuration Change is initiated. In this Configuration Change, some parameters are resetted (for example Par 212Fh - Q-Histogramm).

Note: Only a 0 can be written to this Parameter, all other values generates an error response.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Pump is a Slave
1 Pump is a Single Pump
2 Pump is a Double or Multipump Master with one Slave
3 Pump is a Multipump Master with 2 Slaves
4 Pump is a Multipump Master with 3 Slaves
5 Pump is a Multipump Master with 4 Slaves
6 Pump is a Multipump Master with 5 Slaves
Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: 1, n/a
Permission: rwr PDO: yes

In the case of a Single Pump, This Parameter is always 1.
In the case of a Double Pump - Master, This Parameter is always 2.

2070h - Pump Digital Outputs

This Parameter contains all extern outputs present on the pump. This parameter is pump-specific, all the outward physical connection in the pump are represented here. In the case of a relay, the status is if it is active, not if it is open or closed (an active Normally-open relay is closed, and an active Normally-closed relay is open).

Note: If the output is located on an external module (IF-Module) and this is not inserted. The corresponding bits are not possible to read (N/A).

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

2070h Bit 0 - SSM Relay

If the SSM Relay is active this Bit is set to 1.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This Pump.

2070h Bit 1 - SBM Relay

If the SBM Relay is active this Bit is set to 1. In Stratos if no IF-Module with SBM function is present, this bit is undefined.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This Pump.

2072h - Pump Digital Inputs

This Parameter contains all extern inputs present on the pump. This parameter is pump-specific, all the inward physical connections in the pump are represented here

Note: If the input is located on an external module (IF-Module) and this is not inserted. The corresponding bits are not possible to read (N/A).

Variable Type: UNSIGNED8, RAM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

2072h Bit 0 - Extern Off

If the Extern Off signal at the pump is active, this bit is set to 1. In Stratos if no IF-Module with Ext OFF function is present, this bit is undefined.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This Pump.

2072h Bit 1 - Extern Min

If the Extern Min signal at the pump is active, this bit is set to 1. In Stratos if no IF-Module with Ext Min function is present, this bit is undefined.

In the case of a Single Pump, This Bit contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Bit contains/affects the value of This Pump.

2076h - IF-Module

This Parameter contains information about what IF-Module is inserted in the Pump.

Value Description
0 No IF-Module Inserted
1 IF-PLR or IF-LON Inserted
2 IF-CAN Inserted
3 IF-Ext.Off/Ext.Min/SBM/0-10V Combination Inserted (Stratos only)
Variable Type: UNSIGNED8, RAM Formatting: Select
Value: 0 to 6 Default, Error: 0, 0xFF
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.


Section Measurement

2083h - Speed (DP/MP)

This Parameter returns the speed of the slaves in a double or multi pump system.

SubIndex Name Variable Type Default Value
2083h Subindex 0 Number of Entries UNSIGNED8 calc
2083h Subindex 1 Master Speed UNSIGNED16 0
2083h Subindex 2 Slave 1 or DP Slave Speed UNSIGNED16 0
2083h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2083h Subindex 1 - Master Speed

This Subindex returns the speed of the Master (in a Multi Pump system or in a Double Pump system).

Variable Type: UNSIGNED16, RAM Formatting: 1 rpm
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2083h Subindex 2 - Slave 1 or DP Slave Speed

This Subindex returns the speed of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, RAM Formatting: 1 rpm
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2087h - Estimated Flow (System)

This Parameter returns the estimated flow in the system

Dependency: This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.

Variable Type: UNSIGNED16, RAM Formatting: 0.1 m3/h
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2088h - Estimated Flow Range Min (System)

This Parameter returns the estimated minimum limit of the total estimated flow in the system

Dependency: This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.

Variable Type: UNSIGNED16, RAM Formatting: 0.1 m3/h
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2089h - Estimated Flow Range Max (System)

This Parameter returns the estimated maximum limit of the total estimated flow in the system

Dependency: This Parameter can change if Par 2050h Bit 4 - Q not Computable changes.

Variable Type: UNSIGNED16, RAM Formatting: 0.1 m3/h
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

208Bh - Estimated Pressure (System)

This Parameter contains the calculated pressure in kPa.

Dependency: This Parameter can change if Par 2050h Bit 5 - H not Computable changes.

Dependency: This Parameter is disabled, if the Par 2001h - Pump Control Mode is set to "CONST_CONTROL (PID)".

Dependency: This Parameter is disabled, if the Par 2009h - Bus Control Mode is set to "CONST_CONTROL (PID)".

Variable Type: UNSIGNED16, RAM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

208Ch - Estimated Pressure Range Min (System)

This Parameter returns the estimated minimum limit of the total estimated pressure in the system

Dependency: This Parameter can change if Par 2050h Bit 5 - H not Computable changes.

Dependency: This Parameter is disabled, if the Par 2001h - Pump Control Mode is set to "CONST_CONTROL (PID)".

Dependency: This Parameter is disabled, if the Par 2009h - Bus Control Mode is set to "CONST_CONTROL (PID)".

Variable Type: UNSIGNED16, RAM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

208Dh - Estimated Pressure Range Max (System)

This Parameter returns the estimated maximum limit of the total estimated pressure in the system

Dependency: This Parameter can change if Par 2050h Bit 5 - H not Computable changes.

Dependency: This Parameter is disabled, if the Par 2001h - Pump Control Mode is set to "CONST_CONTROL (PID)".

Dependency: This Parameter is disabled, if the Par 2009h - Bus Control Mode is set to "CONST_CONTROL (PID)".

Variable Type: UNSIGNED16, RAM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2090h - Power Rating (System)

This Parameter contains the input power, in Watts for the pump System.

Note: The resolution of the units, can be far less exact than represented here.

Variable Type: UNSIGNED32, RAM Formatting: 0.001 W
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2091h - Current (System)

This Parameter contains the effective ampere consumption of the System.

Variable Type: UNSIGNED32, RAM Formatting: 0.001 A
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2092h - Voltage Level (DP/MP)

This Parameter contains the actual voltage level for this double or multi pump system.

SubIndex Name Variable Type Default Value
2092h Subindex 0 Number of Entries UNSIGNED8 calc
2092h Subindex 1 Voltage Level (Master) UNSIGNED16 0
2092h Subindex 2 Voltage Level (Slave 1) UNSIGNED16 0
2092h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2092h Subindex 1 - Voltage Level (Master)

This Parameter contains the actual voltage level for the Master (in a Multi Pump system or in a Double Pump system).

Variable Type: UNSIGNED16, RAM Formatting: 1 V
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2092h Subindex 2 - Voltage Level (Slave 1)

This Parameter contains the actual voltage level for the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, RAM Formatting: 1 V
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2093h - Power Rating (DP/MP)

This Parameter contains the input power, in Watts of the slaves in a double or multi pump system.

SubIndex Name Variable Type Default Value
2093h Subindex 0 Number of Entries UNSIGNED8 calc
2093h Subindex 1 Power Rating (Master) UNSIGNED32 0
2093h Subindex 2 Power Rating (Slave 1) UNSIGNED32 0
2093h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2093h Subindex 1 - Power Rating (Master)

This Parameter contains the input power, in Watts of the Master (in a Multi Pump system or in a Double Pump system).

Variable Type: UNSIGNED32, RAM Formatting: 0.001 W
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2093h Subindex 2 - Power Rating (Slave 1)

This Parameter contains the input power, in Watts of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED32, RAM Formatting: 0.001 W
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2094h - Current (DP/MP)

This Parameter contains the effective ampere consumption of the double or multi pump system.

SubIndex Name Variable Type Default Value
2094h Subindex 0 Number of Entries UNSIGNED8 calc
2094h Subindex 1 Current (Master) UNSIGNED32 0
2094h Subindex 2 Current (Slave 1) UNSIGNED32 0
2094h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2094h Subindex 1 - Current (Master)

This Parameter contains the effective ampere consumption of the Master (in a Multi Pump system or in a Double Pump system).

Variable Type: UNSIGNED32, RAM Formatting: 0.001 A
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2094h Subindex 2 - Current (Slave 1)

This Parameter contains the effective ampere consumption of the Slave 1 (in a Multi Pump system) or the DP Slave (in a Double Pump system).

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED32, RAM Formatting: 0.001 A
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

20A0h - Medium Temperature (System)

This Parameter contains the actual medium temperature in degrees Kelvin. This is measured by an internal or external sensor.

Note: If there is no internal sensor in the pumps, the external sensor should be connected to the Master of the DP or MP System. If an external sensor is connected to the master (activated with Par 2200h - Temperature Sensor Source), this will always be used, the internal sensors will be disregarded.

Dependency: This Parameter can change source if Par 2200h - Temperature Sensor Source changes.

Variable Type: UNSIGNED16, RAM Formatting: 0.1 K
Value: 0 to 0xFFFF Default, Error: 273, 0xFFFF
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.


Section Messaging (Service and Errors)

20C1h - Current Warning/Error

This Parameter contains the Current Error or Warning Message, if it has been Acknowledged it is cleared, and if another one happens while one is already displayed, it will be displayed after the next acknowledge (or self correction). In effect, this is the same error message that is displayed on the pump display. To know it this message is a Warning or Error Message Par 2052h Bit 3 - Warning Present or Par 2052h Bit 4 - Error Present must be checked.

Note: This Parameter is reset on a power loss.

Value Description
0 No Error
1 E01
2 E02
3 E03
n E0n
... ...
Variable Type: UNSIGNED8, RAM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, 0x00
Permission: ro PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

20C2h - Current Warning/Error (DP/MP)

This Parameter contains the Current Warning Message for all slaves, if it has been Acknowledged it is cleared, and if another one happens while one is already displayed, it will be displayed after the next acknowledge. See the Par 20C1h - Current Warning/Error for a description of the values of this Parameter.

Note: This Parameter is reset on a power loss.

SubIndex Name Variable Type Default Value
20C2h Subindex 0 Number of Entries UNSIGNED8 calc
20C2h Subindex 1 Current Warning/Error (Master) UNSIGNED8 0
20C2h Subindex 2 Current Warning/Error (Slave 1) UNSIGNED8 0
20C2h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

20C2h Subindex 1 - Current Warning/Error (Master)

This Subindex returns the Last Error (Master), in a Multi Pump system or in a Double Pump system.

Variable Type: UNSIGNED8, RAM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, 0x00
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

20C2h Subindex 2 - Current Warning/Error (Slave 1)

This Subindex returns the Last Error (Slave 1), in a Multi Pump system or in a Double Pump system.

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED8, RAM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, 0x00
Permission: ro PDO: yes

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

20E0h - Error History Code (Master)

This Parameter Array contains the error that has happened (with history), the first object (Subindex 1) is always the last one. A maximum of 16 Errors are stored here. If an Error occurrs it is written here and the Error status bit ( Par 2052h Bit 4 - Error Present) is going high.

Note: An Error cannot be written here without an EMCY message being sent. If any EMCY Messages were sent during the reading of these Parameters, This Parameter may have shifted, and should be read again.

Note: The error List can be cleared by sending the Value 0 to Par 20E0h Sub 0 - Number of Entries, no other values are accepted. This also clears the Par 20E6h - Error History Date (Master) and Par 20ECh - Error History Operation Hours (Master).

SubIndex Name Variable Type Default Value
20E0h Subindex 0 Number of Entries UNSIGNED8 calc
20E0h Subindex 1 Error_t UNSIGNED8 0
20E0h Subindex 2 Error_t-1 UNSIGNED8 0
20E0h Subindex 3 Error_t-2 UNSIGNED8 0
20E0h Subindex 4 Error_t-3 UNSIGNED8 0
20E0h Subindex 5 Error_t-4 UNSIGNED8 0
20E0h Subindex 6 Error_t-5 UNSIGNED8 0
20E0h Subindex 7 Error_t-6 UNSIGNED8 0
20E0h Subindex 8 Error_t-7 UNSIGNED8 0
20E0h Subindex 9 Error_t-8 UNSIGNED8 0
20E0h Subindex 10 Error_t-9 UNSIGNED8 0
20E0h Subindex 11 Error_t-10 UNSIGNED8 0
20E0h Subindex 12 Error_t-11 UNSIGNED8 0
20E0h Subindex 13 Error_t-12 UNSIGNED8 0
20E0h Subindex 14 Error_t-13 UNSIGNED8 0
20E0h Subindex 15 Error_t-14 UNSIGNED8 0
20E0h Subindex 16 Error_t-15 UNSIGNED8 0
20E0h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes. This number is always the number of stored Error messages.

Variable Type: UNSIGNED8, EEPROM Formatting: Number
Value: 0 to calc Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

20E0h Subindex 1 - Error_t

This Subindex contains the last error code.

Value Description
01 E01
02 E02
03 E03
... etc...
Variable Type: UNSIGNED8, EEPROM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

20E0h Subindex 16 - Error_t-15
Value Description
01 E01
02 E02
03 E03
... etc...
Variable Type: UNSIGNED8, EEPROM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

20E1h - Error History Code (Slave 1)

This Parameter Array contains the error that has happened (with history), the first object (Subindex 1) is always the last one. A maximum of 16 Errors are stored here. If an Error occurrs it is written here and the Error status bit ( Par 2052h Bit 4 - Error Present) is going high.

Note: An Error cannot be written here without an EMCY message being sent. If any EMCY Messages were sent during the reading of these Parameters, This Parameter may have shifted, and should be read again.

Note: The error List can be cleared by sending the Value 0 to Par 20E1h Sub 0 - Number of Entries, no other values are accepted. This also clears the Par 20E7h - Error History Date (Slave 1) and Par 20EDh - Error History Operation Hours (Slave 1).

SubIndex Name Variable Type Default Value
20E1h Subindex 0 Number of Entries UNSIGNED8 calc
20E1h Subindex 1 Error_t UNSIGNED8 0
20E1h Subindex 2 Error_t-1 UNSIGNED8 0
20E1h Subindex 3 Error_t-2 UNSIGNED8 0
20E1h Subindex 4 Error_t-3 UNSIGNED8 0
20E1h Subindex 5 Error_t-4 UNSIGNED8 0
20E1h Subindex 6 Error_t-5 UNSIGNED8 0
20E1h Subindex 7 Error_t-6 UNSIGNED8 0
20E1h Subindex 8 Error_t-7 UNSIGNED8 0
20E1h Subindex 9 Error_t-8 UNSIGNED8 0
20E1h Subindex 10 Error_t-9 UNSIGNED8 0
20E1h Subindex 11 Error_t-10 UNSIGNED8 0
20E1h Subindex 12 Error_t-11 UNSIGNED8 0
20E1h Subindex 13 Error_t-12 UNSIGNED8 0
20E1h Subindex 14 Error_t-13 UNSIGNED8 0
20E1h Subindex 15 Error_t-14 UNSIGNED8 0
20E1h Subindex 16 Error_t-15 UNSIGNED8 0
20E1h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes. This number is always the number of stored Error messages.

Variable Type: UNSIGNED8, EEPROM Formatting: Number
Value: 0 to calc Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of MP Slave 1.

20E1h Subindex 1 - Error_t

This Subindex contains the last error code.

Value Description
01 E01
02 E02
03 E03
... etc...
Variable Type: UNSIGNED8, EEPROM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of MP Slave 1.

20E1h Subindex 16 - Error_t-15
Value Description
01 E01
02 E02
03 E03
... etc...
Variable Type: UNSIGNED8, EEPROM Formatting: Error Code
Value: 0 to 0xFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of MP Slave 1.


Section Statistic

2101h - Operation Time Resettable (System)

This Parameter returns the time from the System where at least one pump was running (including the time it runs in peak load), or in the case of a Single Pump, the Operation Time of the Single Pump.

Note: If this parameter is resetted (written to 0) the Par 2104h - Operation Peak Load Time Resettable is also completely resetted. All other Values are not accepted.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2103h - Operation Time Resettable

This Parameter contains the individual running time for each unit of the system (peak load is included and counted only once). This means that if the Master was running alone for 5h and then together with Slave 1 for another 3h, the Master would have a total individual time of 8h (480 minutes) and Slave 1 would have 3h (180 minutes).

SubIndex Name Variable Type Default Value
2103h Subindex 0 Number of Entries UNSIGNED8 calc
2103h Subindex 1 Operation Time Resettable (Master) UNSIGNED32 0
2103h Subindex 2 Operation Time Resettable (Slave 1) UNSIGNED32 0
2103h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2103h Subindex 1 - Operation Time Resettable (Master)

This Parameter counts the time that the Master pump was running (including the time it runs in peak load).

Note: This Parameter is only for the Master pump, if another pump in the same DP or MP system runs, then another value is incremented.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2103h Subindex 2 - Operation Time Resettable (Slave 1)

This Parameter counts the time that the Slave 1 pump was running (including the time it runs in peak load).

Note: This Parameter is only for the Slave 1 pump, if another pump in the same DP or MP system runs, then another value is incremented.

Dependency: CAN write access to This Subindex is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: rw PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2104h - Operation Peak Load Time Resettable

This Parameter contains the total time that 1 or more DP, MP Pumps has been running (peak load time). A sum of all these values would tell you how long this pump has acted as Master in this system where at least one pum was running.

Note: If Master is exchanged, swapped with one of the Slaves or replaced by a new pump, these values are lost.

SubIndex Name Variable Type Default Value
2104h Subindex 0 Number of Entries UNSIGNED8 calc
2104h Subindex 1 One pump running UNSIGNED32 0
2104h Subindex 2 Two pumps running UNSIGNED32 0
2104h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves almost exactly as the Par 206Eh - Number of DP/MP Pumps, the difference is that in the case of a Single Pump ( P206Eh = '1'), This Parameter is '0'.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 0.
In the case of a Double Pump - Master, This Subindex is always 2.

2104h Subindex 1 - One pump running

This Parameter counts the time that one pump in the DP or MP System was running. If more than one pump were running, this parameter is not incremented.

Note: This value is not incremented if the pump is running as a Single Pump.

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2104h Subindex 2 - Two pumps running

This Parameter counts the time that two pumps in the DP or MP System was running. If less or more than two pumps were running, this parameter is not incremented.

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2108h - Power On Time

This Parameter counts the total time that this pump had power.

Note: This Parameter is only for the current pump, if another pump in the same DP or MP system has power, then another value is incremented.

SubIndex Name Variable Type Default Value
2108h Subindex 0 Number of Entries UNSIGNED8 calc
2108h Subindex 1 Power On Time (Master) UNSIGNED32 0
2108h Subindex 2 Power On Time (Slave 1) UNSIGNED32 0
2108h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2108h Subindex 1 - Power On Time (Master)

This Parameter counts the total time that this pump had power.

Note: This Parameter is only for the Master pump, if another pump in the same DP or MP system runs, then another value is incremented.

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2108h Subindex 2 - Power On Time (Slave 1)

This Parameter counts the total time that this pump had power.

Note: This Parameter is only for the Slave 1 pump, if another pump in the same DP or MP system runs, then another value is incremented.

Variable Type: UNSIGNED32, EEPROM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2109h - Uptime

This Parameter counts the total time that this pump had power since the last reset or power off.

Note: This Parameter is only for the current pump, if another pump in the same DP or MP system has power, then another value is incremented.

Variable Type: UNSIGNED32, RAM Formatting: 1 Minutes
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2110h - Power On Counter

This Parameter contains the number of times the software has booted (reset is included in the count). This counter can be cleared by writing the Value 0, no other values are accepted.

SubIndex Name Variable Type Default Value
2110h Subindex 0 Number of Entries UNSIGNED8 calc
2110h Subindex 1 Power On Counter (Master) UNSIGNED16 0
2110h Subindex 2 Power On Counter (Slave 1) UNSIGNED16 0
2110h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2110h Subindex 1 - Power On Counter (Master)

This Parameter contains the number of times the software has booted (reset is included in the count).

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2110h Subindex 2 - Power On Counter (Slave 1)

This Parameter contains the number of times the software has booted (reset is included in the count).

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2111h - Pump Kick Counter

This Parameter contains the number of pump kicks that has been activated. All Pump Kicks are counted disregarding from where they were initiated (the automatic ones, set with Par 2251h - Pump Kick Time and those that are initiated with Par 2250h - Pump Kick Event).

SubIndex Name Variable Type Default Value
2111h Subindex 0 Number of Entries UNSIGNED8 calc
2111h Subindex 1 Pump Kick Counter (Master) UNSIGNED16 0
2111h Subindex 2 Pump Kick Counter (Slave 1) UNSIGNED16 0
2111h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2111h Subindex 1 - Pump Kick Counter (Master)

This Parameter contains the number of pump kicks that has been activated in the Master (in case of a DP/MP Pump) or Single Pump. This counter can be cleared by writing the Value 0, no other values are accepted.

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2111h Subindex 2 - Pump Kick Counter (Slave 1)

This Parameter contains the number of pump kicks that has been activated in this specific Slave. This counter can be cleared by writing the Value 0, no other values are accepted.

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2112h - Auto Night Mode Counter

This Parameter contains the number of started automatic night mode.

Note: Must be implemented if the Automatic Night Mode is implemented.

SubIndex Name Variable Type Default Value
2112h Subindex 0 Number of Entries UNSIGNED8 calc
2112h Subindex 1 Auto Night Mode Counter (Master) UNSIGNED16 0
2112h Subindex 2 Auto Night Mode Counter (Slave 1) UNSIGNED16 0
2112h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2112h Subindex 1 - Auto Night Mode Counter (Master)

This Parameter contains the number of started automatic night mode. This counter can be cleared by writing the Value 0, no other values are accepted.

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2112h Subindex 2 - Auto Night Mode Counter (Slave 1)

This Parameter contains the number of started automatic night mode. This counter can be cleared by writing the Value 0, no other values are accepted.

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, EEPROM Formatting: Number
Value: 0 to 0xFFFF Default, Error: 0, 0xFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

2113h - Consumption (System)

This Parameter contains the power consumption in kWh for this System.

Variable Type: UNSIGNED32, EEPROM Formatting: 0,1 kWh
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2114h - Consumption

This Parameter contains the power consumption in kWh for this pump.

SubIndex Name Variable Type Default Value
2114h Subindex 0 Number of Entries UNSIGNED8 calc
2114h Subindex 1 Consumption (Master) UNSIGNED32 0
2114h Subindex 2 Consumption (Slave 1) UNSIGNED32 0
2114h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2114h Subindex 1 - Consumption (Master)

This Parameter contains the power consumption in kWh for this pump. This counter can be cleared by writing the Value 0, no other values are accepted.

Variable Type: UNSIGNED32, EEPROM Formatting: 0,1 kWh
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2114h Subindex 2 - Consumption (Slave 1)

This Parameter contains the power consumption in kWh for this pump. This counter can be cleared by writing the Value 0, no other values are accepted.

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED32, EEPROM Formatting: 0,1 kWh
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

212Fh - Q-Histogramm

This Parameter contains statistical data, in order to see where the pump is working in the moment. This Parameter array can have different resolutions, but each value is always an n-th of the total range (5 values, gives each percentage a 20% share of the flow range). This Array can be reset if one of the subindexes is written to 0.

Note: Before the data of this parameter is read, the Number of Entries must be read in order to know how many colums are present and which ranges they have.

Note: The Par 21A7h - Max Flow must be used in order to present the maximum Flow (Qmax) in the diagram.

Note: In the case that this pump has not yet been running, the percentages are all set to 0. In the case of a DP or MP Pump, this parameter collects data for the complete System.

Note: The values here are resetted if the pump changes configuration (for example from Single Pump to Double Pump, or from a Multi Pump with 2 Slaves to to a Multi Pump with 3 Slaves). See Par 206Eh - Number of DP/MP Pumps for information when a configuration change can occur.

Note: This Parameter is also reset on Factory Reset and if the running mode is changed (Peak mode or Main/reserve mode)

SubIndex Name Variable Type Default Value
212Fh Subindex 0 Number of Entries (n) UNSIGNED8 5
212Fh Subindex 1 Histogram 0% - 20% UNSIGNED16 0
212Fh Subindex 2 Histogram 20% - 40% UNSIGNED16 0
212Fh Subindex 3 Histogram 40% - 60% UNSIGNED16 0
212Fh Subindex 4 Histogram 60% - 80% UNSIGNED16 0
212Fh Subindex 5 Histogram 80% - 100% UNSIGNED16 0
212Fh Subindex 0 - Number of Entries (n)

This Subindex contains the number of following subindexes.

Variable Type: UNSIGNED8, EEPROM Formatting: Number
Value: 0 to 0xFF Default, Error: 5, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 5.
In the case of a Double Pump - Master, This Subindex is always 5.

212Fh Subindex 1 - Histogram 0% - 20%

This Subindex contains the percentage in which the pump was driven in this interval

Variable Type: UNSIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

212Fh Subindex 2 - Histogram 20% - 40%

This Subindex contains the percentage in which the pump was driven in this interval

Variable Type: UNSIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

212Fh Subindex 3 - Histogram 40% - 60%

This Subindex contains the percentage in which the pump was driven in this interval

Variable Type: UNSIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

212Fh Subindex 4 - Histogram 60% - 80%

This Subindex contains the percentage in which the pump was driven in this interval

Variable Type: UNSIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.

212Fh Subindex 5 - Histogram 80% - 100%

This Subindex contains the percentage in which the pump was driven in this interval

Variable Type: UNSIGNED16, EEPROM Formatting: 0.01 Percent
Value: 0 to 0x7FFF Default, Error: 0, 0x7FFF
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of This System.


Section Constants

2182h - Pump Type

This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index. Single or Double Pumps have the same type, they are not differentiated.

Note: This parameter is required so that the configuration program knows what profile to load.

Note: VDMA: part of ProductIdentifier (see Par 2180h - Manufacturer Version for the other part).

SubIndex Name Variable Type Default Value
2182h Subindex 0 Number of Entries UNSIGNED8 calc
2182h Subindex 1 Pump Type (Master) UNSIGNED16 0
2182h Subindex 2 Pump Type (Slave 1) UNSIGNED16 0
2182h Subindex 0 - Number of Entries

This Subindex contains the number of following subindexes.

Note: This Subindex behaves exactly as the Par 206Eh - Number of DP/MP Pumps.

Variable Type: UNSIGNED8, RAM Formatting: Number
Value: 0 to 6 Default, Error: calc, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Subindex is always 1.
In the case of a Double Pump - Master, This Subindex is always 2.

2182h Subindex 1 - Pump Type (Master)

This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index. Single or Double Pumps have the same type, they are not differentiated.

Note: If this is changed, Par 1018h Sub 2 - Product Code must be changed as well.

Value Description
0x00-- No Pump Family
0x01-- Stratos
0x--00 No Pump Type
0x0110 (272) Stratos 25/1-6
0x0111 (273) Stratos 30/1-6
0x0112 (274) Stratos 40/1-4
0x0113 (275) Stratos 25/1-8
0x0114 (276) Stratos 30/1-8
0x0120 (288) Stratos 25/1-12
0x0121 (289) Stratos 30/1-12
0x0122 (290) Stratos 40/1-8
0x0123 (291) Stratos 50/1-8
0x0124 (292) Stratos 32/1-12
0x0130 (304) Stratos 40/1-12
0x0131 (305) Stratos 50/1-12
0x0132 (306) Stratos 50/1-9
0x0133 (307) Stratos 65/1-9
0x0140 (320) Stratos 65/1-12
0x0141 (321) Stratos 80/1-12
0x0142 (322) Stratos 100/1-12
Variable Type: UNSIGNED16, EEPROM Formatting: Select
Value: 0 to 0xFFFF Default, Error: 0, 0
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Subindex contains/affects the value of the System Master.

2182h Subindex 2 - Pump Type (Slave 1)

This Parameter contains the specific pump type. The High byte describes the Pump Family and the low byte describes the Pump with an index. Single or Double Pumps have the same type, they are not differentiated. See Par 2182h Sub 1 - Pump Type (Master) for values.

Note: If the Slave 1 (or DP Slave) is disconnected or not present, this Parameter will contain the Error Value.

Variable Type: UNSIGNED16, RAM Formatting: Select
Value: 0 to 0xFFFF Default, Error: 0, 0
Permission: ro PDO: no

In the case of a Single Pump, This Subindex contains the Error Value.
In the case of a Double Pump - Master, This Subindex contains/affects the value of DP Slave.

218Bh - Pump Type Name

This Parameter contains the Name of this pump. It changes depending on what value is written in the Par 2180h - Manufacturer Version.

Note: VDMA: DeviceType

Note: In Stratos this field is intern limited to 16 UniCode characters. The length of this string is maximum 64 bytes (32 UniCode characters).

Variable Type: UNICODE_STRING, ROM Formatting: Version
Value: 0 to 32 Default, Error: "", n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

218Ch - This Pump Function

This Parameter user configureable, it contains the name of the function of the pump in the building or basement. The name must be limited to 16 UniCode characters or 32 ASCII characters.

Note: VDMA: TechPlaceFunction

Example: 'Heating'

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNICODE_STRING, EEPROM Formatting: Text
Value: 0 to 16 Default, Error: "", n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

218Dh - This Pump Location/Name

This Parameter user configureable, it contains the name of the place where the pump is located in the building or basement. The name must be limited to 16 UniCode characters or 32 ASCII characters.

Note: VDMA: TechPlaceLocation

Example: 'Basement C'

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNICODE_STRING, EEPROM Formatting: Text
Value: 0 to 16 Default, Error: "", n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A0h - Min Speed (System, CONST_SPEED)

The minimal possible speed of the pump in rpm.

Variable Type: UNSIGNED16, ROM Formatting: 1 rpm
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A1h - Max Speed (CONST_SPEED)

The max possible speed of the pump in rpm.

Variable Type: UNSIGNED16, ROM Formatting: 1 rpm
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A4h - Min Pressure dp-v (VAR_DIFFPRESS)

The min possible pressure in dp-v mode of the pump in kPa.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A5h - Max Pressure dp-v (VAR_DIFFPRESS)

The max possible pressure in dp-v mode of the pump in kPa.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A7h - Max Flow

The max possible flow of the pump in m3/h

Variable Type: UNSIGNED16, ROM Formatting: 0.1 m3/h
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A8h - Min Medium Temperature

This Parameter contains the min allowable medium temperature for this pump.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 K
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21A9h - Max Medium Temperature

This Parameter contains the max allowable medium temperature for this pump.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 K
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21ABh - Max Power Rating

This Parameter contains the max possible powerconsumption of the pump in Watts.

Variable Type: UNSIGNED32, ROM Formatting: 0.001 W
Value: 0 to 0xFFFFFFFF Default, Error: 0, 0xFFFFFFFF
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21ACh - Min Pressure dp-c (CONST_DIFFPRESS)

The min possible pressure in dp-c mode of the pump in kPa.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

21ADh - Max Pressure dp-c (CONST_DIFFPRESS)

The max possible pressure in dp-c mode of the pump in kPa.

Variable Type: UNSIGNED16, ROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.


Section Configuration

2201h - dp-c = f(T) Regulation Tmin

This Parameter sets the minimum temperature for Temperature Regulation. Since this value must always be atleast 10 degrees smaller than Par 2202h - dp-c = f(T) Regulation Tmax, the value in Par 2202h - dp-c = f(T) Regulation Tmax is always set to 10 degrees Kelvin higher than this value if it previously was lower.

Note: Low Limit is equal to Par 21A8h - Min Medium Temperature and High Limit is equal to Par 21A9h - Max Medium Temperature.

Dependency: This Parameter can change source if Par 2200h - Temperature Sensor Source changes.

Dependency: This Parameter can change value if Par 2202h - dp-c = f(T) Regulation Tmax changes.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting: 0.1 K
Value: 0 to 0xFFFF Default, Error: 3231, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2202h - dp-c = f(T) Regulation Tmax

This Parameter sets the maximum temperature for Temperature Regulation. Since this value must always be atleast 10 degrees higher than Par 2201h - dp-c = f(T) Regulation Tmin, the value in Par 2201h - dp-c = f(T) Regulation Tmin is always set to 10 degrees Kelvin lower than this value if it previously was higher.

Note: Low Limit is equal to Par 21A8h - Min Medium Temperature and High Limit is equal to Par 21A9h - Max Medium Temperature.

Dependency: This Parameter can change source if Par 2200h - Temperature Sensor Source changes.

Dependency: This Parameter can change value if Par 2201h - dp-c = f(T) Regulation Tmin changes.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting: 0.1 K
Value: 0 to 0xFFFF Default, Error: 3631, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2203h - dp-c = f(T) Regulation Pmin

This Parameter sets the wanted pressure at Tmin for Temperature Regulation. This value can be lower or higher than Par 2204h - dp-c = f(T) Regulation Pmax, depending on wanted function.

Note: Default value is equal to Par 21ACh - Min Pressure dp-c (CONST_DIFFPRESS).

Dependency: This Parameter can change source if Par 2200h - Temperature Sensor Source changes.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2204h - dp-c = f(T) Regulation Pmax

This Parameter sets the wanted pressure at Tmax for Temperature Regulation. This value can be lower or higher than Par 2203h - dp-c = f(T) Regulation Pmin, depending on wanted function.

Note: Default value is in middle of Par 21ACh - Min Pressure dp-c (CONST_DIFFPRESS) and Par 21ADh - Max Pressure dp-c (CONST_DIFFPRESS).

Dependency: This Parameter can change source if Par 2200h - Temperature Sensor Source changes.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting: 0.1 kPa
Value: 0 to 0xFFFF Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2207h - HV/AC System Error Detection

This Parameter configures the pump to be used as a heating (HV) or air conditioning (AC) pump. It changes the number of Errors until an Final Error occurs.

Note: The slave always contains the value from the master.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Heating, Ventilation (Final Error on n=6)
1 Air Conditioning (Final Error on n=1)
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2208h - Error Auto Reset Time

This Parameter changes the auto reset time for all Errors that uses one. All other Errors remain unchanged. The auto reset time is the time at which the pump resets itself after the error has been issued. Normally this time is 5 minutes, and since the Final Error is first signalled with the 6th Error, this would take about 30 minutes. This Parameter can shorten that time.

Note: All Slaves uses the same Value as the Master

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED16, EEPROM Formatting: 1 s
Value: 10 to 300 Default, Error: 300, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2229h - Automatic Night Mode

This Parameter sets the speed or pressure of the pump during Automatic Night Mode. It is only active if pressure regulation is chosen ( Par 2001h - Pump Control Mode equal to CONST_PRESSURE, CONST_DIFFPRESS or VAR_DIFFPRESS), if the Par 2056h Bit 0 - LON/PLR Controlled is 0 and if Par 2235h - 0-10V Activate is 0.

Note: 2,3 etc... uses the min values from pressureMin, SpeedMin etc

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 disabled
1 auto
2 pressure(zukunft)
3 speed(zukunft)
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2232h - SBM Relay Mode

This Paramater can change the behaviour of the SBM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:

Note: With This Parameter, you can configure the SBM relays as the customer ses fit, for example: Read for Operation or Rotating.

Note: This Parameter affects the Master only, the Slaves behaviour will not change.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Relay always off
1 Pump Ready, Pull when this pump is ready (power on and no error)
2 Pump Operating, Pull when this pump is operating (default)
3 System Ready, Pull when at least one DP/MP pump is ready (power on and no error), Slave Relays are always only for this pump
4 System Operating, Pull when at least one DP/MP pump is operating (power on and rotating), Slave Relays are always only for this pump.
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 4 Default, Error: 2, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2233h - SSM Relay Mode

This Paramater can change the behaviour of the SSM contact in the pump (it does not modify the behaviour of the I/O-Module). The trigger corresponds to the following:

Note: With This Parameter, you can configure the SSM relays as the customer ses fit, for example: on Warning or on Error.

Note: This Parameter affects the Master only, the Slaves behaviour will not change.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Relay always off
1 Pump Warning, Pull when this Pump has a Warning, Error or Final Error
2 Pump Error, Pull when this pump has an Error or Final Error
3 Pump Final Error, Pull when this pump has a Final Error (default)
4 System Warning, Pull when at least one DP/MP pump has a Warning, Error or Final Error, Slave Relays are always only for this pump.
5 System Error, Pull when at least one DP/MP pump has an Error or Final Error, Slave Relays are always only for this pump.
6 System Final Error, Pull when at least one DP/MP pump has a Final Error, Slave Relays are always only for this pump.
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 6 Default, Error: 3, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2234h - 0-10V Setpoint Mode

This Parameter controls the Zero setpoint Mode of the 0-10V in. If the setpoint is below the min-value of the pump the pump goes to the following states.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Pump Off, pump turns off at this low level and turns back on at min level, with a predefined hysteresis (default).
1 Pump Min, the pump stays at minimal value for the chosen control mode.
2 Linear, the distibution between 0 to 100% and min to max are liniar. (Not implemented in Stratos).
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2235h - 0-10V Activate

This Parameter controls the activation of the 0-10V in.

Note: It is only possible to set this Parameter to 1, if a IF-Module Stratos (in the case of a Stratos Pump) is inserted and the control Mode is not TEMP_VARIABLE. If no If-Module is inserted (in the case of a Stratos Pump) or the current mode is TEMP_VARIABLE, an error will be issued (0800 0020h).

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 0-10V Off (default).
1 0-10V On
Variable Type: UNSIGNED8, EEPROM Formatting: Bit
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2250h - Pump Kick Event

This Parameter activates the pump kick function. If the value 1 is written, the pump (or System) briefly runs in order to avoid problem arising from standing still too long. This is only possible if the Pump has no error present.

Note: This Parameter is default 0, if the value 1 is written, the function is executed and automatically returned to 0.

Note: All Slaves runs simultaneously with the Master if this is activated.

Note: If this value is written, the Pump Kick Time is NOT resetted (see Par 2251h - Pump Kick Time).

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, RAM Formatting: Event
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2251h - Pump Kick Time

This Parameter contains how oft the pump kick is to be initiated. the value is the number of consecutive 'non running hours' between pump kicks.

Note: If this value is written, the Pump Kick Time is resetted (it starts counting from 0).

Note: If this Parameter is set to a time larger than 24 hours or Off, the Par 2250h - Pump Kick Event must be used regularely (at least every 24 hours). A Pump returned on warranty, with problems arising from this Parameter being set wrongly may cancel the warranty.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
1 to 127 Number of 'non running hours' between two pump kicks.
0 pump kick disabled.
Variable Type: SIGNED8, EEPROM Formatting: Hour
Value: 0 to 127 Default, Error: 24, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

225Bh - Menu lock

This Parameter locks the menu completely. By some pumps this can also be activated/deactivated by a DIP-Switch inside the pump.

Value Description
0 Normal Access
1 Menu locked
Variable Type: UNSIGNED8, EEPROM Formatting: Bit
Value: 0 to 1 Default, Error: 0, n/a
Permission: ro PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This Pump.

225Dh - Display Orientation

This Parameter can change the orientation of the Display. The default orientation, and the orientation rotation (90 or 180 degrees) depends on the pump type. In the case of a Pump system, all displays are rotated simultaneously.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Not rotated (product defined default)
1 Rotated (product defined)
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

225Eh - Display Unit

This Parameter controls the unit displayed in the pump display.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 mWS
1 feet
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.


Section Double/Multi Pump

2315h - DP-Modus

This Parameter sets the Double Pump Mode in the pump system. Peak Load Mode allowes for higher flow, because if one pump is not enought, the second start running. In Master-Reserve Mode, both pumps never run at the same time and if one would fail the other takes over very quickly. This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.

Dependency: This Parameter is disabled, if the Par 2316h - Pump Housing is set to "0".

Value Description
0 Master-Reserve (default)
1 Peak Load
Variable Type: UNSIGNED8, EEPROM Formatting: Select
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This System.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2320h - Pump Swap Event

This Parameter is automatically resetted to zero as soon as the function has returned, it has been written as '1', and will read as a zero when the event has taken place. Writing this parameter to a '1' activates the Pump Swap Function, simultaneously the time to the next swap is reset. The next free spare pump will be chosen in the case of a MP System. Writing this Parameter to 0 is not allowed.

Note: This Parameter is not related to Operation Hours or any other Parameter.

Note: In the case of a MP there is a rule how the next pump is chosen, see Par 2311h - Number Reserve Pumps (MP only), Par 2312h - Fixed Reserve Pumps (MP only) and Par 2314h - Pump Absolute Distribution (MP only).

Example: If the Pump Swap Event is to happen in the next hour it will still happen in the next hour even if this parameter is used.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, RAM Formatting: Event
Value: 0 to 1 Default, Error: 0, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2322h - Pump Swap Time (DP/MP)

This Parameter contains how oft the pump swap is to be initiated. the value is the number of running hours between pump swaps.

Note: If this value is written, the Pump Swap Time is resetted (it starts counting from 0). There is no other way to reset this counter during normal operation.

Note: This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
1 to 127 Number of running hours between two pump swaps
0 automatic pump swap disabled.
Variable Type: SIGNED8, EEPROM Formatting: 1 Hour
Value: 0 to 127 Default, Error: 24, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This System.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.

2323h - Member Pump Enable

Note: This Parameter can be written even if the current pump is a single pump, if this pump later becomes a master this setting becomes valid for the complete system.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Bit Bit equals Zero Bit equals One
0 Master Enable Master Disable
1 Slave1 Enable Slave1 Disable
2 Slave2 Enable Slave2 Disable
3 Slave3 Enable Slave3 Disable
4 Slave4 Enable Slave4 Disable
5 Slave5 Enable Slave5 Disable
Variable Type: UNSIGNED8, EEPROM Formatting: Bitset
Value: 0 to 0xFF Default, Error: 0xFF, n/a
Permission: rww PDO: yes

In the case of a Single Pump, This Parameter contains/affects the value of This System.
In the case of a Double Pump - Master, This Parameter contains/affects the value of This System.


Section CAN Configuration

2400h - CANopen Address

This is the CANopen address (1-127). This Parameter only makes sense if an IF-Module-CAN is inserted. The value 0 turns the CAN bus off. To turn it on again the value should be set to the wanted address.

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Variable Type: UNSIGNED8, EEPROM Formatting: CANAddress
Value: 0 to 127 Default, Error: 1, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.

2403h - Auto Operational Mode

the wait time before the pump goes into the Operational mode. this time starts to count down when the first foreign heartbeat is seen on the bus.

Note: If this value is 0, the NMT Auto Operational mode is deactivated

Dependency: CAN write access to This Parameter is disabled, if the Par 2056h Bit 4 - Local Operation Active is set to "1".

Value Description
0 Auto Operational Off
1-255 Auto Operational in x Seconds
Variable Type: UNSIGNED8, EEPROM Formatting: 1 s
Value: 0 to 0xFF Default, Error: 5, n/a
Permission: rw PDO: no

In the case of a Single Pump, This Parameter contains/affects the value of This Pump.
In the case of a Double Pump - Master, This Parameter contains/affects the value of the System Master.





Wilo AG, Generated at 04.06.2008 09:30:09