SINGLE AND DOUBLE IN-LINE PUMPS WITH ONE-PIECE DESIGN

For the circulation of abrasive residue-free heating, cooling or iced water in collective residential and tertiary buildings.

TECHNICAL SPECIFICATIONS

Flow rate of up to : 120 m3/h
Manometric head of up to: : 31 mWC
Max. operating pressure on discharge: : 10 bar
Fluid temperature limit : -20 to +110°C
Max. ambient temperature : 40°C
DN pipe union ports : 1" to 11/4" (U version)
DN round-flanged ports : DN 25 to DN 80
Mains supply : 3~230 V (<3 kW), 3~400 V, 50 Hz
P2 power : Up to 4 kW
Simple or Normal/Backup and Cascade configuration : 1 or 2 motor units
Regulation mode : Fixed speed

APPLICATIONS

For the circulation of abrasive residue-free heating, cooling or iced water in collective residential and tertiary buildings.

BENEFTIS

  • Energy savings
    Compatible with external speed variation
  • Easy installation
    Compact, one-piece pump requiring little space
  • Easy maintenance
    Completely maintenance-free, standardised mechanical seal to +110°C max.
    Bearings lubricated for life
  • Pump protection
    IP 55 protection class for the electrical part of the motor
    Corrosion-resistant cataphoretic coating
    Seizing-resistant impeller made from composite material
  • Acoustic comfort
    Quiet operation

DESIGN

  • Motor
    IE2 motor featuring asynchronous technology (IE3 on demand), with an extended shaft
  • Hydraulics
    Single stage in-line pump with one-piece design
    Single and double cast-iron, cataphoretic-coated housings equipped with bosses as standard
    Seizing-resistant 2D hydraulics made from composite material
    Pressure taps fitted as standard on flanged models

Documents

 

ACCESSORIES

  • Differential pressure kit
  • Bracket for mounting on base plate (DN 65 and DN 80 models)
  • PN 10/16 round, solder-on counter-flanges
  • Shut-off valves
  • Drip cover (specify when ordering)
  • YN 1200, CC-HVAC and CCE-HVAC monitoring and control box
  • Sealing cover
  • Vibration damping sleeves
selecson