AXIALLY SPLIT PUMP

For the circulation of abrasive residue-free heating, cooling or iced water in urban systems.

TECHNICAL SPECIFICATIONS

Flow rate of up to : 17,000 m3/h
Manometric head of up to: : 170 mWC
Max. operating pressure on discharge: : 25 bar
Fluid temperature limit : -8 to +120°C
Max. ambient temperature : 40°C
DN round-flanged ports : DN 150 to DN 500
Mains supply : 3~400 V, 50 Hz
P2 power : Up to 630 kW
Simple configuration : Possibility of back-up or cascade mode
Regulation mode : Fixed speed

APPLICATIONS

For the circulation of abrasive residue-free heating, cooling or iced water in urban systems.

BENEFTIS

  • Energy savings
    Compatible with external speed variation
    Optional: CERAM CT coating to improve pump efficiency
  • Easy installation
    Cast-iron frame as standard for a more rigid assembly
  • Easy maintenance
    Access to rotating parts without needing to remove the motor, bearings or hydraulic connections
    Spacer facilitates removal of the motor
    Sealed bearings lubricated for life
  • Pump protection
    Vibration-damping design of rotating pump components (shaft and impeller)
    Option: corrosion-resistant cataphoretic coating
    Very low NPSH for greater suction capacity

DESIGN

  • Motor
    Standardised IE2 motor featuring asynchronous technology (IE3 on demand)
  • Hydraulics
    Single-stage or two-stage axially split pump, with single or double volute
    Cast-iron or ductile cast-iron, stainless steel or bronze housing mounted on a rigid frame
    Cast-iron, bronze or stainless steel 2D hydraulics.
    Impeller diameter can be adapted to optimise the duty point